Zhone IMACS-200 ユーザーズマニュアル

ページ / 294
11-4 
Alarm Ports
Model No.
Running Head
Alarm port User Screens and Settings
Alarm ports
Table 11-1. Alarm Contacts Main Screen Actions
Table 11-2. Alarm Contacts Settings and Defaults
SWITCH
The Switch setting indicates that the outbound alarm switch is actv (on) or stdby (off).
ACT ON
The Act On parameter defines the type of system alarm that will cause the switch to trigger. 
Program each alarm switch to trigger on minor (information and minor) alarms, major (major 
and critical) alarms, or any alarm message.
SENSOR
The Sensor setting indicates the inbound alarm sensor is actv (on) or stdby (off).
TRIG ON
The Trigger On parameter defines if the sensor should report an external alarm upon sensing 
the opening (open) or the closure (close) of the external contact to which it is connected.
Action
Function
Save
Saves changes to settings.
Undo
Returns all settings to the last saved state.
Refresh
Updates certain time-related information fields that are not automatically 
updated on screen (i.e., alarm data).
Main
Returns to the System Main Screen. If changes are made to settings and 
not saved, you will be prompted to save or lose changes.
Parameter
User Options
Default
SWITCH
stdby     actv
stdby
ACT ON
minor     major     any
minor
SENSOR
stdby     actv
stdby
TRIG ON
close     open
close