13 - GENERAL INSTRUCTIONS
Figure 18 - Gas Burner Flame
Figure 20 - Gas Burner Pilot
Figure 19 - Combustion Chamber
BURNERS
ORIFICES
GAS VALVE
• Make visual inspection of main burner and pilot flames 
at start of heating season and again in mid-season. Main 
burner flame should have well defined inner blue mantel 
with lighter blue outer mantel. Check burner throats and 
burner orifices for lint or dust obstruction. Figures 18 
and 19.
• Pilot flame should envelop ⅜ to ½ inch of tip of ignition/
sensing electrode.  See Figure 20.
• To adjust pilot flame, remove pilot adjustment cover 
screw and turn inner adjustment screw counterclockwise 
 to increase or clockwise 
 to decrease pilot 
flame. Be sure to replace cover screw after adjustment to 
prevent possible gas leakage. See Figure 16, Page 19.
• Check burners and pilot for signs of corrosion, rust or 
scale buildup. 
• Area around boiler must be kept clear and free of 
combustible materials, gasoline and other flammable 
vapors and liquids.
• Free flow of combustion and ventilating air to boiler and 
boiler room must not be restricted or blocked.
• Inspect field sourced low water cutoffs annually, or 
as recommended by low water cutoff manufacturer.  
Flush float type low water cutoffs per manufacturer's 
instructions.
• Employ a qualified service agency to make annual 
inspection of boiler and heating system. They are 
experienced in making the inspections outlined above, 
and, in event repairs or corrections are necessary, 
trained technicians make the proper changes for safe 
operation of the boiler.