Utica Boilers JE インストール手順

ページ / 36
10
6. 
In calculating free area using louvers, grilles or 
screens for above, consideration shall be given 
to their blocking effect. Screens used shall not be 
smaller than 1/4 inch mesh. If free area through 
design of louver or grill is known, it should be used 
in calculating size opening required to provide free 
area specified. If design and free area is not known, 
it may be assumed that wood louvers will have 20-
25% free area and metal louvers and grilles will 
have 60-75% free area. Louvers and grilles should 
be fixed in open position or interlocked with boiler 
so they are opened automatically during boiler 
operation.
1. 
The vent pipe must slope upward from the boiler 
not less than 1/4” for every 1’ to the vent terminal. 
Figures 1 & 2.
2. 
Horizontal portions of the venting system shall be 
supported rigidly every 5 feet and at the elbows. No 
portion of the vent pipe should have dips or sags.
Flue Connection And Venting
Vent installations shall be in accordance with “Venting of 
Equipment”, of the National Fuel Gas Code, ANSI Z223.1/
NFPA 54, or applicable provisions of the local building 
codes.
1. 
Consult dimensional drawing for number and size of  
flue pipes required for each size boiler.
2. 
Maintain minimum upward slope of 1/4 inch per linear  
foot from the boiler to chimney.
3. 
Run flue pipe directly as possible. Keep turns to a 
minimum. Insert flue pipe into, but not beyond, inside 
wall of chimney. Do not connect into a chimney serving 
an open fireplace.
4. 
Insulate flue pipe where it passes near combustible  
material.
5. 
Rigidly support pipe with hangers and straps.
6. 
Extend chimneys at least 2 feet above any object  
within radius of 15 feet, including roof.
7. 
Install hood on all flue pipes which extend through roof. 
In most locations, venting of boiler relies on natural 
draft. In as much as energy available from natural 
draft is quite low, serious thought should be given to 
vent system design, i.e., adequate size, use of gradual 
transitions, tees, elbows, etc., close proximity of boiler 
and chimney. On all boilers, vertical risers must be at 
least as large as vent openings on draft-hood. Boiler 
manufacturer makes no specific recommendations 
regarding application of draft inducers that may be 
used with this boiler. If draft inducer is used, it is up to 
installing contractor and draft inducer manufacturer to 
determine proper application.
VENTILATION  AND COMBUSTION AIR
A.  When installing two openings, one must commence 
within 12 inches from top and other within 12 
inches from bottom of enclosure. Openings shall 
communicate directly, or by ducts, with outdoors 
or spaces (crawl or attic) that freely communicate 
with outdoors. One of following methods must be 
used to provide adequate air for ventilation and 
combustion.
1) When directly communicating with outdoors, 
each opening shall have minimum free area of 
1 square inch per 4,000 Btu per hour of total 
input rating of all equipment in enclosure. Refer 
to Figure 2 on previous page.
2)  When communicating with outdoors by 
means of vertical ducts, each opening shall 
have minimum free area 1 square inch per 
4,000 Btu per hour of total input rating of all 
appliances in the enclosed space.
3)  If horizontal ducts are used, each opening 
and duct shall have minimum free area 1 
square inch per 2,000 Btu per hour of total 
input rating of all appliances in the enclosed 
space.
VENT INSTALLATION
B.  One permanent opening, commencing within 12 
inches of top of enclosure, shall be permitted where 
equipment has clearances of at least 1 inch from 
sides, 1 inch from back, and 6 inches from front 
of boiler. Opening shall directly communicate with 
outdoors or shall communicate through vertical 
or horizontal duct to outdoors or spaces (crawl 
or attic) that freely communicate with outdoors. 
Openings must have minimum free area of 1 
square inch per 3000 Btu per hour of total input 
rating of all equipment located in enclosure. Free 
area must be no less than sum of areas of all vent 
connectors in confined space.
 WARNING
Vent connectors serving appliances vented by 
natural draft shall not be connected into any 
portion of mechanical draft systems operating 
under positive pressure.
!