Utica Boilers JE インストール手順

ページ / 36
9
Important Vent-Piping Note: Sloped vent pipe at 
least 1/4” for every 1’ to the vent terminal.
1. 
Provide combustion and ventilation air in accordance 
with the section “Air for Combustion and Ventilation”, 
of the National Fuel Gas Code, ANSI Z223.1/NFPA 54, 
or applicable provisions of the local building codes.
2. 
Boiler is located in unconfined space in building or 
conventional construction frame, masonry or metal 
building, infiltration normally is adequate to provide air 
for combustion and ventilation. However, if equipment 
is located in building of tight construction (See National 
Fuel Gas Code, ANSI Z223.1), boiler area should be 
considered as confined space. If there is any doubt, 
install air supply provisions in accordance with latest 
revision of National Fuel Gas Code.
3. 
Boiler is installed in unconfined space, in building of 
tight construction, air for combustion and ventilation 
must be obtained from outdoors or from spaces freely 
communicating with outdoors. Permanent opening 
or openings having total free area of not less than 1 
square inch per 5,000 Btu per hour of total input rating 
of all appliances shall be provided. Ducts may be used 
to convey makeup air from outdoors and shall have 
same cross-sectional area of openings to which they 
are connected.
4. 
When air for combustion and ventilation is from inside 
buildings, confined space shall be provided with two 
permanent openings, one starting 12 inches from top 
and one 12 inches from bottom of enclosed space. Each 
opening shall have minimum free area of 1 square inch 
per one thousand (1000) Btu per hour of total input 
rating of all appliances in enclosed space, but must 
not be less than one hundred (100) square inches. 
Openings must freely communicate directly with other 
spaces of sufficient volume so combined volume of all 
spaces meets criteria for unconfined space. Figure 1.
5. 
When boiler is installed in confined space and all 
air is provided from outdoors confined space shall 
be provided with one or two permanent openings 
according to methods A or B (see page 10). When 
ducts are used, they shall be of same cross sectional 
area as free area of area of openings to which they 
connect. Minimum dimension of rectangular air ducts 
shall be not less than 3 x 3 inches or 9 square inches.
Vent-Piping
Combustion 
Air
Openings
Combustion Air supplied from 
inside the building
Vent-Piping
Combustion Air
Openings with 
Motorized Dampers
Combustion Air supplied from 
outside the building
VENTILATION  AND COMBUSTION AIR
Figure 1 
Figure 2