Diagnostics data 
 
6.1 Diagnostics by means of LED displays 
 
D410 
136
 
Commissioning Manual, 08/2008 Edition 
LED displays 
The following table provides an overview of all relevant LED display combinations. Each LED 
can be lit in yellow, red, or green color. The color which corresponds with the LED signal 
state is also defined. 
Table 6-2 
Diagnostics by means of LED display 
Meaning 
RDY 
RUN/STOP
OUT > 5V 
SF/BF: 
SINAMICS Integrated ready for operation 
 (green) 
SINAMICS Integrated in fault state 
Λ 
(red) 
Startup of the D410 without CF card or with CF card without valid 
operating system (the bootloader may be defective) 
0,5/1 
(red) 
(red) 
Write access to CompactFlash Card 
2/1 
 (green) 
SIMOTION ready for operation 
 (green or 
yellow) 
Fault event to which the user program (SIMOTION) cannot 
respond, or firmware error at the PROFINET interface. 
The following actions may be required to rectify the fault: 
• 
Power OFF/ON 
• 
Check of the CompactFlash Card 
• 
Re-commissioning 
• 
Replacement of SIMOTION D410 
Λ 
(red) 
Λ 
(red) 
Λ 
(red) 
A warning is present on the SINAMICS Integrated.  
This state can occur, for example, when the DRIVE-CLiQ 
components are loaded but have not been inserted.  
(yellow) 
 
Ethernet LED (only for SIMOTION D410 PN) 
DCP flashing of the module activated in the HW Config at Target 
system > Ethernet > Edit Ethernet node > "Search" button > 
"Flashing" button  
Priority: 0 
1)
 
2/1 
 (green) 
Active interrupt which can be acknowledged (alarm, message, 
note) 
Priority: 1 
1)
 
(red) 
Bus fault 
• 
PROFIBUS master: At least one slave is missing 
• 
PROFIBUS slave: No parameter assignment master found 
• 
PROFINET: Failure of a connected I/O device; at least one of 
the assigned I/O devices cannot be addressed; faulty or 
missing configuration data. 
Priority: 2 
1)
 
2/1 
(red) 
Sublicensing of technology/option objects 
Priority: 3 
1)
 
0.5/1 
(red) 
Upgrade/downgrade operation running. 
0,5/1 
 (yellow)