Diagnostics data 
 
6.1 Diagnostics by means of LED displays 
D410 
Commissioning Manual, 08/2008 Edition 
137
 
Meaning 
RDY 
RUN/STOP  OUT > 5V 
SF/BF: 
The upgrade/downgrade operation has completed 
(power OFF/ON of the upgraded/downgraded devices is 
necessary) 
2/1 
 (yellow) 
 
STOP to RUN transition 
2/1 
 (green) 
STOP/STOPU 
 (yellow) 
RUN to STOP transition 
2/1 
 (yellow) 
Memory reset requested by SIMOTION D410, or by means of 
mode selector switch. 
0,5/1 
 (yellow) 
Memory reset in progress 
Memory reset completed 
 (yellow) 
 
Firmware download to the integrated PROFINET interface is busy 
2/1 
 (yellow) 
2/1 
 (yellow) 
Firmware download to the integrated PROFINET interface is 
completed SIMOTION cannot enter the RUN and Online mode 
 (green) 
 (yellow) 
Λ 
(red) 
1)
 Priority of the displays: The displays always visualize the state which is assigned the 
numerically lowest priority level. The error of the next highest priority class is displayed after 
the cause of the previous signal state was eliminated. 
The LED "OUT > 5V" display is controlled only by the encoder evaluation for the integrated 
X23 encoder interface in SINAMICS Integrated. The table below lists the display states and 
their meaning. 
Table 6-3 
LED display OUT > 5V 
Status 
Meaning 
Electronic power supply is missing or outside the valid tolerance range. Power 
supply ≤ 5 V. Use of an encoder with 5 V power supply. 
 (yellow) 
Electronics power supply for measuring system available. Power supply >5 V. 
Caution: Always ensure that you can operate the encoder on the 24 V power 
supply (e.g. HTL encoder). Operation of a 5 V encoder on the 24 V encoder 
supply may lead to the destruction of its electronic components! This setting can 
be selected in the expert list of the drive in parameter p405.1.