Service Manual
Third edition, June 1997
9.12
Draft measurement
9.12.1 Draft measurement incorrect
Failure on LevelDatic equipment
• Check LevelDatic equipment. See separate documentation in "As-
built drawings and user's manual"-binder.
Incorrectly configured data for draft measurement.
• Check that configured ship data in Ship measures-window on Work
Station correspond to real distances on ship.
Faulty communication with LevelDatic equipment.
• See chapter 9.1.10.
9.13
Load Calculator
9.13.1 Values displayed on TankRadar and load calculator differ.
Ullage values differ due to a delay of information during quick loading or
discharging, especially in small tanks.
• When the surface is stable, wait for approximately one minute to see
that the values become equal.
• Concentrate on ullage values displayed on TankRadar since they are
updated more often than on the load calculator.
Trim/List correction is set to off on Work Station, but the protocol to the
load calculator is using trim/list corrected values.
• Check setting of trim/list correction in the Setup-window. See
Operating Manual.
Presentation units changed from m to feet or vice versa.
• Check setting of units in the Setup-window. See Operating Manual.