LOOP INSTALLATION 
 
1.  Layout the desired loop locations per the diagram.  
The standard size chart below will give an 
approximate length of wire required for various loop 
dimensions and number of turns required. 
 
CAUTION:  The Loop wires and Lead-in wires must be a 
continuous piece of wire without splices. The amount of lead 
in wire required must be added to these lengths for total wire 
required. Only use wire intended for this type of application. 
(Type XHHW insulation 16AWG) 
 
NOTE: Buried steel from drains or other systems may affect 
functioning of the loop system. Check with the factory for 
advice on any special installations.  (1-800-243-4476). 
 
STANDARD LOOP LAYOUTS 
FOR APPROX 36” HEIGHT DETECTION 
 
LOOP SIZE 
# OF TURNS 
LOOP WIRE 
LENGTH (FT) 
4’X4’ 4 
64’ 
4’ X 6’ 
80’ 
4’ X 8’ 
72’ 
4’ X 10’ 
84’ 
4’ X 12’ 
96’ 
4’ X 14’ 
108’ 
4’ X 16’ 
120’ 
4’ X 18’ 
132’ 
4’ X 20’ 
144’ 
4’ X 22’ 
156’ 
4’ X 24’ 
168’ 
4’ X 26’ 
180’ 
4’ X 28’ 
192’ 
4’ X 30’ 
136’ 
4’ X 32’ 
144’ 
4’ X 34’ 
152’ 
4’ X 36’ 
160’ 
4’ X 38’ 
168’ 
4’ X 40’ 
176’ 
 
32 
2. Cut the required groove as shown in the diagram below 
at the locations laid out in Step #1. 
 
 
3/16" To 1/4"
1" To 2"
1" To 2"
Loop Wire
(See Chart)
Lead In Wire
(Twisted At 6
Turns Per Foot)
1/2" Conduit
Conduit Cut