Patterson-Kelley MACH-05 ユーザーズマニュアル

ページ / 59
  MACH®  Series
 
Gas-Fired Boiler 
Installation 
 
 
Page  14 
 
Pipe Capacity for Natural Gas 
 
Equivalent Pipe Length 
 
Maximum Capacity in Cubic Feet of Natural Gas per Hour 
Pressure Drop of 0.5 inch Water Column/Equivalent Length of Pipe 
(in feet) 
Nominal 
Iron Pipe 
Size 
(Inches) 
 
Internal 
Diameter 
(Inches) 
90º Ell 
(Feet) 
Tee 
(Feet) 
 
20 
 
40 
 
60 
 
80 
 
100 
 
150 
 
200 
1/2 0.622 1.55 
3.1  120 82 66 57 50 40 35 
3/4  0.824  2.06 
4.12  250 170 138 118 103  84  72 
1  1.049  2.62 
5.24  465 320 260 220 195 160 135 
1- 1/4 
1.380 
3.45 
6.9 
950 660 530 460 400 325 280 
1- 1/2 
1.610 
4.02 
8.04  1460 990 810 690 620 500 430 
2.067 
5.17 
10.3 
2750 1900 1520 1300 1150  950  800 
2- 1/2 
2.469 
6.16 
12.3 
4350 
3000 2400 2050 1850 1500 1280 
3.068 
7.67 
15.3 
7700 5300 4300 3700 3250 2650 2280 
4.026 
10.1 
20.2  15800 
10900 8800 7500 6700 5500 4600 
 
 
 
3.7.1  Gas Supply Piping by Installer 
The boiler and all gas piping connections should be 
pressure-tested and must be checked for leaks before 
being placed into service.  Test with compressed air or 
inert gas if possible. 
The boiler must be disconnected at the boiler manual 
shut-off valve (located at the end of the supplied gas 
train) from the gas supply piping system during any 
pressure testing of the system at pressures in excess of 
1/2 psig (14" W.C.). 
During any pressure testing of the gas supply piping 
system at pressures equal to or less than 1/2 psig (14" 
W.C.), the boiler should be isolated from the gas 
supply piping system by closing the manual shut-off. 
Some leak test solutions, including soap and water, 
may cause corrosion.  These solutions should be 
rinsed-off with water after testing. 
 
3.8
  
B
OILER 
W
ATER 
P
IPING
 
 
3.8.1  Piping Design 
 
Water Flow in System 
For proper water flow requirements see below.  
Incorrect flow may result in eventual damage or 
premature failure of the equipment. 
 
Model Max 
Flow 
GPM 
Min Flow 
GPM 
DP ft. at 
max flow 
1050 105  52  12 
900 90  45  12 
750 75  37  12 
450 45  22  8.5 
300 30  15  8.5 
 
 
Contact factory for minimum flow at other than 
maximum firing rate.