Patterson-Kelley MACH-05 ユーザーズマニュアル

ページ / 59
  MACH®  Series
 
Gas-Fired Boiler 
Installation 
 
 
Page  21 
First Digit 
Boiler Status 
delay.  No system call for heat. 
Burner off - Domestic Hot Water pump 
running on delay.  No system call for heat. 
9 and b 
flashing 
Burner off – auto reset lockout.  A code is 
displayed indicating the reason for the 
lockout.  (See Troubleshooting Section 
5.5.) 
Adjusting the 3 way valve if used 
Burner on in manual high fire 
Burner on in manual low fire 
 
Parameter Mode: 
The parameter mode is used to change the settings of 
the boiler.  The parameter mode is accessed by 
pressing the MODE key several times until the display 
shows PArA
The parameters are selected with the STEP key, and 
changed with the plus “+” and minus “-“ keys.  Once 
the desired value is reached, pressing the STORE key 
accepts the new setting.   
Parameters 1 through 4 are accessible directly at the 
parameter level.   
Parameters higher than 4 are only accessible by 
authorized service personnel trained on the P-K 
MACH Series Boiler. 
 
Parameter Description  Lower 
Limit 
Upper 
Limit 
DHW setpoint 
if used 
68° 158° 
2 DHW 
system 
ON/OFF 
0=OFF 
1=ON 
2=OFF +pump 
continuous 
3=ON + pump 
continuous 
 
3 Comfort 
heat 
system 
ON/OFF 
0=OFF 
1=ON 
2=OFF +pump 
continuous 
3=ON + pump 
continuous  
Setpoint or 
max boiler 
temp outdoor 
air mode 
68° 182° 
Information Mode: 
The information mode is used to display the values of 
the various sensors such as inlet water temp, outlet 
water temp etc. The information mode is accessed by 
pressing the MODE key several times until InFo is 
displayed.  The desired sensor is selected with the 
STEP key.  The following table indicates the 
displayed value: 
 
 
Step Value 
1 Outlet 
water 
temp 
2 Inlet 
water 
temp 
Domestic Hot Water temp *  
Outdoor air temp * 
Flue gas temp 
Boiler outlet setpoint 
Rate of change outlet temp  °F/second 
Rate of change inlet temp  °F/second 
Rate of change Domestic Hot Water 
°F/second 
Second Comfort Heat system 
temperature 
 
 
* If the sensors for these functions are not installed, 
the display will indicate -22
 
3.12.1.2  Operating Configurations 
The boiler has several different operating 
configurations.  These are:  
•  Internal Setpoint 
•  Domestic Priority 
•  Outdoor Air Reset 
•  Analog Input Setpoint 
•  Analog Input Direct Drive 
 
 
CAUTION!  
Do not modify any parameters other than those 
specifically mentioned.