Maintenance 
 
 
Page  35 
5.5.2  Auto-reset Service Codes 
 
Code Lockout 
Description 
b 08 
Air pressure switch open. 
The air pressure switch failed to close to indicate sufficient air flow to start the boiler. 
b 18 
Outlet high limit temp. 
The outlet water temperature has exceeded the internal high limit temperature setting. 
b 19 
Return high limit temp. 
The return water temperature has exceeded the internal high limit temperature setting. 
b 24 
Switched inlet / outlet. 
The inlet water temperature has been more than 18° F above the outlet for more than 
75 seconds. 
b 25 
Outlet temp rapid change. 
The outlet water temperature is increasing too fast.  Indicating low flow condition. 
b 26 
High exhaust back pressure. 
The high exhaust back pressure switch is tripped indicating a blocked stack, inlet, or 
condensate system. 
b 30 
Max delta T. 
The temperature rise across the heat exchanger is greater than maximum allowed, 
indicating insufficient flow. 
b 40 
Flue sensor open. 
The flue gas temperature sensor is indicating an open circuit. 
b 52 
High flue temp. 
The flue temperature has exceeded the maximum allowable setting. 
b 61 
Air pressure switch closed. 
The air pressure switch failed to open prior to starting the blower. 
b 65 
Fan speed incorrect. 
The fan is being directed to a higher speed than it is achieving. 
 
 
 
 
 
 
WARNING 
 
If any “Manual Reset” limit device trips, 
DO NOT 
reset without determining and correcting the cause.