Toshiba VF-AS1 ユーザーズマニュアル

ページ / 326
!
  E6581301 
J-3 
10 
 Selection of wiring equipment
Voltage
class
Applicable 
motor [kW]
Inverter model
Input current[A] 
Molded  Case  Circuit  Breaker
  (MCCB) 
Magnetic  contactor   
(MC) 
Without 
Reactor
With   
Reactor
Without 
Reactor
With 
Reactor
Without 
Reactor
With 
Reactor
Rated current
[A]
Rated current
[A]
Operationl 
current [A]
AC-1 
Operationl 
current [A]
AC-1 
200V 
class 
0.4 
VFAS1-2004PL 
3.5 
2.1 
25 
25 
0.75 
VFAS1-2007PL 
6.1 
3.2 
10 
25 
25 
1.5 
VFAS1-2015PL 
11.3 
6.4 
15 
10 
25 
25 
2.2 
VFAS1-2022PL 
15 
9.3 
20 
15 
25 
25 
3.7/4.0 
VFAS1-2037PL 
25.8 
15.5 
30 
30 
32 
25 
5.5 
VFAS1-2055PL 
35 
22. 5 
50 
40 
40 
25 
7.5 
VFAS1-2075PL 
45 
34.5 
60 
40 
50 
40 
11 
VFAS1-2110PM 
53.3 
75 
80 
15 
VFAS1-2150PM 
-!
71.7 
-!
100 
-!
80 
18.5 
VFAS1-2185PM 
-!
77 
-!
100 
-!
80 
22 
VFAS1-2220PM 
-!
88 
-!
125 
-!
125 
30 
VFAS1-2300PM 
-!
124 
-!
150 
-!
125 
37 
VFAS1-2370PM 
-!
141 
-!
175 
-!
250 
45 
VFAS1-2450PM 
-!
167 
-!
200 
-!
250 
55 
VFAS1-2550P 
-!
200 
-!
250 
-!
275 
75 
VFAS1-2750P 
-!
271 
-!
350 
-!
350 
400V 
class 
0.75 
VFAS1-4007PL 
3.7 
2.1 
25 
25 
1.5 
VFAS1-4015PL 
5.8 
3.8 
10 
6.3 
25 
25 
2.2 
VFAS1-4022PL 
8.2 
5.7 
14 
10 
25 
25 
3.7/4.0 
VFAS1-4037PL 
14.1 
8.7 
18 
14 
25 
25 
5.5 
VFAS1-4055PL 
20.3 
12.7 
32 
25 
25 
25 
7.5 
VFAS1-4075PL 
27 
16.3 
32 
25 
32 
25 
11 
VFAS1-4110PL 
36.6 
21.5 
50 
30 
40 
32 
15 
VFAS1-4150PL 
48 
33.5 
60 
40 
50 
40 
18.5 
VFAS1-4185PL 
45.5 
60 
50 
22 
VFAS1-4220PL 
-!
50 
-!
60 
-!
50 
30 
VFAS1-4300PL 
-!
66 
-!
100 
-!
80 
37 
VFAS1-4370PL 
-!
84 
-!
100 
-!
125 
45 
VFAS1-4450PL 
-!
104 
-!
125 
-!
125 
55 
VFAS1-4550PL 
-!
120 
-!
150 
-!
125 
75 
VFAS1-4750PL 
-!
167 
-!
200 
-!
250 
90 
VFAS1-4900PC 
-!
166 
-!
200 
-!
250 
110 
VFAS1-4110KPC 
-!
202 
-!
250 
-!
275 
132 
VFAS1-4132KPC 
-!
238 
-!
300 
-!
315 
160 
VFAS1-4160KPC 
-!
289 
-!
350 
-!
350 
200 
VFAS1-4200KPC 
-!
356 
-!
500 
-!
500 
220 
VFAS1-4220KPC 
-!
396 
-!
500 
-!
500 
280 
VFAS1-4280KPC 
-!
494 
-!
700 
-!
700 
355 
VFAS1-4355KPC 
-!
636 
-!
1000 
-!
1000 
400 
VFAS1-4400KPC 
-!
707 
-!
1000 
-!
1000 
500 
VFAS1-4500KPC 
-!
875 
-!
1200 
-!
1600 
(*1): Selections for use of the Toshiba 4-pole standard motor with power supply voltage of 200V/400V-50Hz. 
(*2): Choose the MCCB according to the power supply capacity. 
For comply with UL and CSA standard, use the fuse certified by UL and CSA. 
(*3): When using on the motor side during commercial-power supply operation, choose the MC with class AC-3 rated current 
for the motor rated current. 
(*4): Attach surge killers to the magnetic contactor and exciting coil of the relay. 
(*5): In the case the magnetic contactor (MC) with 2a-type auxiliary contacts is used for the control circuit, raise the reliability 
of the contact by using 2a-type contacts in parallel connection. 
(*6): For 200V/55kW model and larger and 400V/90kW model and larger, be sure to install a DC reactor.