Toshiba VF-AS1 ユーザーズマニュアル

ページ / 326
!
  E6581301 
J-5 
10 
10.4 
Application and functions of options 
Separate type options shown below are prepared for the inverter VF-AS1 

No-fuse 
breaker 
(MCCB)
N.F
motor
IM
Magnetic
contactor
(MC)
Power supply
(1) Input AC reactor 
(ACL)
(3) EMC filter for CE 
compliance 
(2) DC reactor 
(DCL)
(4) Braking resistor 
VF-AS1
(5) Motor end surge voltage 
suppression filter (for 400V 
models only)
(6) Control power supply 
backup option
(4) Braking resistor/Braking unit 
(200kW models and larger) 
Sorts of separate-type options 
No.
Option name 
Function, purpose. 
(1)
Input  AC  reactor 
(ACL) 
To be used for improvement of input power-factor of the inverter power source, for reducing 
higher harmonic or suppressing external surge. The input reactor can be installed when the 
power capacity is 500 kVA or more and it is 10 times or more as high as the inverter capacity 
or there are some source distorted wave generation such as a thyristor, etc. and a high 
capacity inverter connected with the same distribution system. 
The DC reactor is superior to the input AC reactor in power-factor improvement. For the 
inverter system that is required to be high reliable, it is recommended to use the input AC 
reactor that effectually suppresses external surge together with the DC reactor. 
200V/11 to 45kW models and 400V/18.5 to 75kW models come with a built-in DC rector as 
standard equipment. 
* If you are using a 200V/55kW model or larger or a 400V/90kW model or larger, be sure to 
connect a DC reactor. (No DC reactor is required when the inverter is powered from a DC 
power supply.) 
(2)
DC reactor(DCL) 
(3)
EMC Directive 
compliant noise 
reduction filter 
(EMF3-*****) 
If EMC filter is installed in proper connection, the inverter has consistency with EMC 
commands. 200V/0.4kW to 200V/7.5kW models and 400V/0.75 to 400V/500kW models come 
standard with built-in noise filters. The effectiveness of the built-in filter can, however, be 
increased by adding an EMC filter. 
(4)
Braking  resistor 
Braking  unit 
To be used to shorten deceleration time for the reason of frequently operated quick 
deceleration and suspension or high inertia load. This increases consumption of 
regenerative energy in dynamic braking.  !
For 200kW more inverter, it requires the braking unit. 
(5)
Motor end surge voltage 
suppression filter 
(for 400 V models only)
In a system in which 400 V class general motor is driven by a voltage PWM type inverter 
using a high-speed switching device (IGBT, etc.), surge voltage depending on cable constant 
may cause deterioration in insulation of motor winding. Take measures against surge voltage 
such as use of insulation-reinforced motor, installation of AC reactor, surge voltage 
suppression filter, sine wave filter and so on in the inverter’s output side. 
Note) Set the carrier frequency to 4.0~8.0kHz when sine wave filter is used. 
(6)
Control power supply 
backup option 
The VF-AS1 supplies control power from the main circuit power supply in it. The optional 
backup unit is designed to supply control power in the event the main circuit power supply 
shuts down. 
The optional backup unit can be used with both 200V and 400V models. 
Unit type: CPS002Z 
Type  of   
reactor 
Effect 
Power-factor 
improvement
Harmonic  suppression 
External  surge   
suppression 
200V,  3.7/4.0kW
  or  less 
Other   
combination 
Input  AC   
reactor 
Effective 
Effective 
Effective 
Effective 
DC  reactor 
Very  effective
Effective 
Very  effective
Not  effective