Toshiba VF-AS1 ユーザーズマニュアル

ページ / 326
!
  E6581301 
J-12 
10
10.6 
Connection of a DC power supply and other electric units 
Besides a three-phase commercial power supply, a single-phase 200V power supply (5.5kW or less) and a DC power 
supply can be connected to the VFAS1 inverter. 
When connecting each of these units, keep in mind the points described in the following sections. 
10.6.1  Connection  of  a  single-phase  200V  power  supply
The table below shows which model to select when operating a three-phase induction motor, using a single-phase 
200V power supply (200-240V, 50/60Hz). 
Input power 
Applicable motor (kW) 
Inverter type 
Single phase   
200~240V 
50/60Hz 
0.4 
VFAS1-2007PL 
0.75 
VFAS1-2015PL 
1.5 
VFAS1-2022PL 
2.2 
VFAS1-2037PL 
3.7 
VFAS1-2055PL 
5.5 
VFAS1-2075PL 
Note: Set the parameter H to  (input phase failure detection mode selection: disabled). 
10.6.2  When  using  the  inverter  along  with  a  DC  power  supply!!!!
Keep the following in mind when connecting a DC power supply to the VFAS1 (PA/+ and PC/- terminals). 
Note 1: An optional initial charger (MCR-2550) is needed for middle- and large-capacity models. 
Note 2: 200V-75kW and 400V-110kW or more models are needed to change the connecting for the cooling fan.   
Note 3: A DC reactor does not need to be connected to the inverter. 
Ÿ
 For details about use in combination with a DC power supply, refer to the instruction manual (E6581432) specified 
in section 6.42. 
Voltage class
Inverter model 
Initial charger (optional) 
Change to connection of 
cooling fan power supply
DC reactor 
200V class 
VFAS1-2004PL~ 
VFAS1-2150PM 
No required 
No required 
No required 
VFAS1-2185PM~ 
VFAS1-2550P 
MCR-2550×1 
No required 
No required 
VFAS1-2750P 
MCR-2550×2 (parallel) 
Required 
No required 
400V class 
VFAS1-4007PL~ 
VFAS1-4185PL 
No required 
No required 
No required 
VFAS1-4220PL~ 
VFAS1-4900PC 
MCR-2550×1 
No required 
No required 
VFAS1-4110KPC 
MCR-2550×1 
Required 
No required 
VFAS1-4132KPC~ 
VFAS1-4220KPC 
MCR-2550×2 (parallel) 
Required 
No required 
VFAS1-4280KPC 
MCR-2550×3 (parallel) 
Required 
No required 
VFAS1-4355KPC, 
VFAS1-4400KPC 
MCR-2550×4 (parallel) 
Required 
No required 
VFAS1-4500KPC 
MCR-2550×5 (parallel) 
Required 
No required 
Note: Set the parameter H to  (input phase failure detection mode selection: disabled).