Toshiba VF-AS1 ユーザーズマニュアル

ページ / 326
!
  E6581301!
L-2 
12
2) Standard specifications (large capacity types)    [Note 1] 
Item 
Specification 
Voltage class 
200V class 
Applicable motor (kW)   
55 
75 
Applicable motor (HP)   
75 
100 
R
a
tin
g
 
Type 
VFAS1- 
Form 
2550P 
2750P 
Output capacity 
(kVA)    [Note 2]
84 
109 
Output current 
(A)   
221 
285 
Output voltage
Three-phase 200V~240V (The maximum output voltage is equal to the input supply voltage.)   
Overload 
current rating 
150%-1 minute, 165%-2 sec. 
El
e
c
tr
ic
a
b
ra
k
in
g
 
Dynamic braking 
circuit   
Built-in dynamic braking drive circuit   
Dynamic braking 
resistor 
An external braking resistor (optional)   
Ÿ
 Rating: Refer to 5.19.   
Po
w
e
s
u
p
p
ly
Voltage-frequency
[Note 3]
Three-phase 200~240V-50/60Hz 
Allowable 
fluctuation 
Voltage + 10% - 15%    [Note 4]        Frequency ±5% 
Protective method 
(IEC60529) 
IP00 Open type    [Note 5] 
Cooling method 
Forced air-cooled 
Cooling fan noise (dBA)
61 
72 
Color 
RAL7016 
EMC filter
External filter (optional) 
DC reactor
Attached DC reactor 
Item 
Specification 
Voltage class 
400V class 
Applicable motor (kW)   
90 
110 
132 
160 
200 
220 
280 
355 
400 
500 
Applicable motor (HP)   
125 
150 
200 
250 
300 
350 
450 
550 
600 
700 
R
a
tin
g
 
Type 
VFAS1- 
Form 
4900PC 
4110KPC
4132KPC
4160KPC
4200KPC
4220KPC
4280KPC
4355KPC
4400KPC
4500KPC
Output capacity 
(kVA)    [Note 2]
136 
164 
197 
239 
295 
325 
419 
511 
578 
717 
Output current 
(A)   
179 
215 
259 
314 
387 
427 
550 
671 
759 
941 
Output voltage
Three-phase 380V~480V (The maximum output voltage is equal to the input supply voltage.) 
Overload 
current rating 
150%-1 minute, 165%-2 sec. 
El
e
c
tr
ic
a
b
ra
k
in
g
 
Dynamic 
braking circuit 
Built-in dynamic braking drive circuit 
External dynamic braking circuit (optional) 
Dynamic braking 
resistor 
An external braking resistor (optional)   
Ÿ
 Rating: Refer to 5.19. 
Po
w
e
s
u
p
p
ly
Voltage-frequency
[Note 3]
[Note 6]
Three-phase 380~440V-50Hz
Three-phase 380~480V-60Hz
Allowable 
fluctuation 
Voltage + 10% - 15%    [Note 4]        Frequency ±5%
Protective method
(IEC60529) 
IP00 Open type    [Note 5] 
Cooling method 
Forced air-cooled 
Cooling fan noise (dBA)
61 
72 
73 
73 
76 
76 
76 
76 
76 
78 
Color 
RAL7016 
EMC filter
Built-in 
DC reactor
Attached DC reactor 
Note 1: For 200V-55kW, 400V-90kW or larger model, be sure to install DC reactor.   
However, this is unnecessary for DC input specifications.   
Note 2: Capacity is calculated at 220V for the 200V models and at 440V for the 400V models. 
Note 3: An external power supply backup available (optional) (Type: CSP002Z) 
Note 4: ±10% when the inverter is used continuously (load of 100%).   
Note 5: Models, 200V-18.5kW or more and 400V-22kW or more, do not have wiring port covers. They have large 
openings, but there is no space to bend the external cables inside the unit.  !
Note 6: Three-phase 380~480V-50/60Hz for 4900PC 
!