Toshiba VF-AS1 ユーザーズマニュアル

ページ / 326
!
  E6581301 
L-3 
12 
3) Common specification   
Item 
Specification 
C
o
n
tr
o
l s
p
e
c
ific
a
tio
n
 
Control system 
Sinusoidal PWM control 
Output voltage adjustment Main circuit voltage feedback control. (Switchable between automatic adjustment/fix/control off) 
Output frequency range 
Setting between 0.01 to 500Hz. Default max. frequency is set to 0.01 to 60Hz.   
Maximum frequency adjustment (30 to 500Hz)   
Minimum setting steps of 
frequency 
0.01Hz: operation panel input (60Hz base),   
0.03Hz: analog input (60Hz base, 11 bit/0 to 10Vdc)   
Frequency accuracy 
Analog input: ±0.2% of the maximum output frequency (at 25±10°C) 
Digital input: ±0.01%±0.022Hz of the output frequency 
Voltage/frequency 
characteristics 
V/f constant, square reduction torque control, automatic torque boost, vector calculation control, base 
frequency adjustment 1, 2, 3, and 4 (25 to 500Hz), V/f 5-point arbitrary setting, torque boost adjustment 
(0 to 30%), start frequency adjustment (0 to 10Hz), stop frequency adjustment (0 to 30Hz)   
Frequency setting signal 
3k
Ÿ potentiometer (possible to connect to 1 to 10kŸ-rated potentiometer) 
0 to 10Vdc (input impedance Zin: 30k
Ÿ)   
0 to ±10Vdc (Zin: 22k
Ÿ)   
4 to 20mAdc (Zin:242
Ÿ)   
Terminal board base 
frequency   
The characteristic can be set arbitrarily by two-point setting. Compliant with 6 types of input; analog input 
(RR, VI/II, RX, AI1, AI2), and pulse input. (*AI1, AI2, pulse input: optional) 
Frequency jump   
3 places. Setting of jump frequency and width.   
Upper and lower limit 
frequencies   
Upper limit frequency: 0 to max. frequency, lower limit frequency: 0 to upper limit frequency   
PWM carrier frequency   
200V-45kW or less, adjustable between 1.0 to 16kHz for 400V-75kW or less 
200V-55kW or less, adjustable between 2.5 to 8kHz for 400V-90kW or more 
PID control 
Adjustment of proportional gain, integral time, differential time and delay filter 
Torque control 
Voltage command input specification: DC 0 to ±10V   
O
p
e
ra
tio
n
 s
p
e
c
ifi
c
a
tio
n
s
 
Acceleration/deceleration 
time 
0.01 to 6000 sec. Selectable from among acceleration/deceleration. times 1, 2, 3 and 4. Automatic 
acceleration/deceleration function. S-pattern acceleration/deceleration 1 and 2 pattern adjustable.   
DC braking 
Adjustment of braking start frequency (0 to 120Hz), braking (0 to 100%) and braking time (0 to 20 sec.). 
With emergency stop braking function and motor shaft fix control function.   
Forward run/reverse run 
[Note 1] 
With F-CC closed to forward run, with R-CC closed to reverse run, with both closed to reverse run. With 
ST-CC opened to coast stop. Emergency stop by panel operation or terminal board.   
Jog run   
[Note 1] 
Jog mode, if selected, allows jog operation from the operation panel   
Jog run operation by terminal board is possible by setting the parameters.   
Preset speed operation   
[Note 1] 
By changing the combination of open/close between S1, S2, S3, RR/S4-CC, set frequency + 15-speed 
operation.   
Selectable between acceleration/deceleration time, torque limit and V/f by set frequency.   
Retry 
Capable of restarting after a check of the main circuit elements in case the protective function is 
activated. Max. 10 times selectable arbitrarily. Waiting time adjustment (0 to 10 sec.)   
Soft stall 
Automatic load reduction control at overloading. (Default: OFF) 
Cooling fan ON/OFF   
The cooling fan will be stopped automatically to assure long life when unnecessary.   
Operation panel key 
operation ON/OFF control
Key prohibition selectable between STOP key only, MODE key only, etc. All key operations can be 
prohibited.   
Regenerative power 
ride-through control 
Possible to keep the motor running using its regenerative energy in case of a momentary power failure. 
(Default: OFF) 
Auto-restart operation   
Possible to restart the motor in coasting in accordance with its speed and direction. (Default: OFF) 
Simplified pattern 
operation   
Possible to select each 8 patterns in 2 groups from 15-speed operation frequency. Max. 16 types of 
operation possible. Terminal board operation/repeat operation possible.   
Commercial inverter 
switching 
Possible to switch operation by commercial power source or inverter 
Light-load high-speed 
operation 
Increases the operating efficiency of the machine by increasing the rotational speed of the motor when it 
is operated under light load.   
Drooping function   
When two or more inverters are used to operate a single load, this function prevents load from 
concentrating on one inverter due to unbalance.   
Override function   
External input signal adjustment is possible to the operation frequency command value.   
Pr
o
te
c
tiv
e
 fu
n
c
tio
n
Protective function 
Stall prevention, current limit, overcurrent, overvoltage, short circuit on the load side, ground fault on the 
load side [Note 5], undervoltage, momentary power failure (15ms or more), non-stop control at 
momentary power failure, overload protection, arm overload at starting, overcurrent on the load side at 
starting, overcurrent and overload at dynamic braking resistance, overheat, emergency stop   
Electronic thermal 
characteristic 
Switchable between standard motor/constant torque VF motor, adjustment of overload protection and 
stall prevention level. 
Reset 
Reset by 1a contact closed (or 1b contact opened), or by operation panel. Or power source OFF/ON. 
This function is also used to save and clear trip records.   
(Continued overleaf)