13. Before making a service call
 - Trip information and remedies
13.1 
Trip causes/warnings and remedies 
When a problem arises, diagnose it in accordance with the following table. 
If it is found that replacement of parts is required or the problem cannot be solved by any remedy described in the 
table, contact your Toshiba distributor. 
[Trip information] 
Error 
code
Description 
Possible causes 
Remedies 
QE
*QER
Overcurrent 
during 
acceleration   
•The acceleration time CEE is too short.
•The V/f setting is improper. 
•A restart signal is input to the 
rotating motor after a momentary 
stop, etc. 
•A special motor (e.g. motor with a 
small impedance) is used. 
•Manual torque boost value (XD) is large.
•There is possibility of ground fault.
•Increase the acceleration time CEE.
•Check the V/f parameter setting. 
•Use WX(Auto-restart) and WXE (Regenerative 
power ride-though control). 
•Increase the carrier frequency EH. 
•Decrease XD setting value. 
•Decrease H (stall prevention level) to 130 
as a guide. 
•Increase EH (carrier frequency) setting value if it 
is set at lower value (2kHz or less). 
•Check the cable and the motor for ground faults.
QE
*QER
Overcurrent 
during 
deceleration 
•The deceleration time FGE is too 
short. (in deceleration) 
•There is possibility of ground fault.
•Increase the deceleration time FGE.
•Check the cable and the motor for ground faults.
QE
*QER
Overcurrent 
during fixed 
speed 
•The load fluctuates abruptly.
•The load is in an abnormal 
condition. 
•There is possibility of ground fault.
•Reduce the load fluctuation.
•Check the load (operated machine).   
•Check the cable and the motor for ground faults.
[Note] QER, QER, 
QER originate from 
causes other than those 
mentioned above. 
•A main circuit elements is defective.
•Overheat protection is activated.
•Contact your Toshiba distributor.
•Check operation of cooling fan. 
•Check cooling fan control mode parameter 
H. 
*QEC
U-phase arm
short-circuit
•A main circuit elements is defective 
(U-phase).
•Contact your Toshiba distributor.
*QEC
V-phase arm
short-circuit 
•A main circuit elements is defective 
(V-phase). 
•Contact your Toshiba distributor.
*QEC
W-phase arm
short-circuit
•A main circuit elements is defective 
(W-phase).
•Contact your Toshiba distributor.
QEN
Loaded side 
overcurrent at 
start time 
•The insulation of the output main 
circuit or motor is defective. 
•The motor has too small 
impedance. 
•The drive circuit board in the 
inverter was damaged. 
•Check the cables and wires for defective 
insulation. 
•Selection of short circuit detection at starting 
parameter H. 
•If this error message appears when a motor is not 
connected to the inverter, the inverter itself may 
be faulty, so contact your Toshiba distributor.
QET
Dynamic braking 
element 
overcurrent   
(200V-55kW or 
larger, 
400V-90kW or 
larger) 
•PB-PA/+ circuit is shorted.
•A resistor with resistance smaller 
than the minimum allowable 
resistance is connected. 
•Parameter RD was set to  or 
without connecting regenerative 
brake or with wire disconnected 
(with dynamic braking).
•Check the impedance wiring for the resistor, etc.
•Contact your Toshiba distributor. 
•Check if regenerative brake is connected. 
•If regenerative brake is not necessary, set 
parameter RD to .
QJ Overheating 
•The cooling fan does not rotate.
•The ambient temperature is too 
high. 
•The vent is blocked up. 
•A heat generating device is 
installed close to the inverter. 
•The thermistor in the unit is 
disconnected.
•Restart the operation by resetting the inverter 
after it has cooled down enough. 
•The fan requires replacement if it does not rotate 
during operation. 
•Secure sufficient space around the inverter. 
•Do not place any heat generating device near the 
inverter. 
•Contact your Toshiba distributor.
QJ
Thermal trip 
stop command 
from external 
device 
•An input signal is impressed at 
control input terminal PTG for 
optional add-on cards. 
•A thermal trip command (input 
terminal function:  or ) is 
issued by an external control 
device.
•The motor is overheated, so check whether the 
current flowing into the motor exceeds the rated 
current. 
* In the event one of the error codes QER to QER and QEC to QEC appears, in which case a main 
circuit component has most probably failed, the only way to reset the inverter is to turn power off and back on. 