Toshiba VF-AS1 ユーザーズマニュアル

ページ / 326
!
  E6581301!
M-3 
13 
(Continued) 
Error 
code
Description 
Possible causes 
Remedies 
G
Emergency stop
•Inverter is stopped by panel 
operation during automatic or 
remote operation. 
•A stop command (input terminal 
function:  or ) is issued by 
an external control device.
•Reset the inverter.
GGREEPROM error
•A data writing error occurs.
•Turn off the inverter, then turn it again. If it does 
not recover from the error, Contact your Toshiba 
distributor. 
GGRInitial read error
•Some internal data is corrupted.
•Power was turned off while V[R
was being set.
•Contact your Toshiba distributor.
•Set V[R again. If the inverter does not recover 
from the error, Contact your Toshiba distributor.
GGRInitial read error •Some internal data is corrupted.
•Contact your Toshiba distributor.
GH
GH Ground fault 
•A current leaked from an output 
cable or the motor to ground.
•Check the cable and the motor for ground faults.
  * 
GRJ
Output phase 
failure 
•A phase failure occurred in the 
output line of the main circuit. 
•The motor is not connected.
•Check the main circuit output line, motor, etc. for 
phase failure. 
•Select output phase failure detection parameter H. 
•Make sure that a motor is connected. 
*
GRJ
Input phase 
failure
•A phase failure occurred in the 
input line of the main circuit.
•Check the main circuit input line for phase failure.
GTTMain unit RAM 
fault
•The control RAM is defective.
•Contact your Toshiba distributor.
GTTMain unit ROM 
fault
•The control ROM is defective.
•Contact your Toshiba distributor.
GTTCPU fault
•The control CPU is defective.
•Contact your Toshiba distributor.
GTT
Interruption of 
operation 
command from 
external control 
device
•A normal communication was not
possible for the time or longer set 
by H. 
•Check the remote control device, cables, etc.
GTTGate array fault •Main gate array is defective.
•Contact your Toshiba distributor.
GTTOutput current 
detector error 
•The main output current detector 
is defective. 
•Contact your Toshiba distributor.
GTTOptional unit 
fault 
•An optional device has failed.
(such as a communication device 
[add-on option])
•Check the connection of optional board(s).
•Refer to instructions of options concerned 
specified in Section 6.42.
GTT
Extended panel 
option. cable is 
broken
•10 seconds disconnection is 
detected  by  the  setting  H=0
(disconnection detection)
•Confirm  the  connection between  extended  panel 
option (RKP002Z,RKP004Z) and inverter. 
GVP Tuning error   
•It was unable to auto tuning 
normally.   
•The internal system error occurred 
during auto tuning.
•Perform auto-tuning 1 again and if the error 
persists, contact your Toshiba distributor. 
GVP Tuning 
detection error 
• Some of H,H,
H and H were not to 
be detected during auto tuning. 
•The capacity of the motor 
connected is 2 notches or more 
smaller than the inverter capacity. 
•The motor connected is not a 
three-phase inductive motor. 
•Tuning is performed while no 
motor is connected. 
•The cables connecting the inverter 
to the motor are too long; they are 
more than 30m in length. 
•Tuning is performed while the 
motor is running.
•Make sure that a motor is connected. 
•Make sure that the motor is at standstill.   
•Perform auto-tuning 1 again and if the error 
persists, perform tuning manually. 
GVP Motor constant 
value error 
• Some detection values of
H,H,H and   
H were beyond the limits of 
normal value. 
•The capacity of the motor 
connected is 2 notches or more 
smaller than the inverter capacity. 
•The motor connected is not a 
three-phase inductive motor. 
•The cables connecting the inverter 
to the motor are too long; they are 
more than 30m in length. 
•Tuning is performed while the 
motor is running. 
•Make sure that the motor is at standstill. 
•Perform auto-tuning 1 again and if the error 
persists, perform tuning manually. 
*Presence or absence of parameter trip can be selected. 
(Continued overleaf)