Toshiba VF-AS1 ユーザーズマニュアル

ページ / 326
!
E6581301!
 Operations
          Warning 
Reference 
Prohibited
•  Do not touch inverter terminals when electrical power is applied to the inverter even if the 
motor is stopped.   
Touching the inverter terminals while power is connected to it may result in electric shock. 
•  Do not touch switches when thands are wet and do not try to clean the inverter with a 
damp cloth.   
Such practices may result in electric shock.   
•  Do not go near the motor in alarm-stop status when the retry function is selected.   
The motor may suddenly restart and that could result in injury.   
Take measures for safety, e.g. attaching a cover to the motor, against accidents when the 
motor unexpectedly restarts.   
•  The inverter is tuned automatically (auto-tuning H=, ) when the inverter is started 
for the first time after setup.   
During auto-tuning, which takes several seconds, the motor is energized, although it is 
standing still. Noise may be produced by the motor during auto-tuning, which, however, 
does not indicate that something is wrong with the inverter or the motor.   
•  Do not set the stall prevention level (H) extremely low.   
If the stall prevention level parameter (H) is set at or below the no-load current of the 
motor, the stall preventive function will always be active and increase the frequency when it 
judges that regenerative braking is taking place.   
Do not set the stall prevention level parameter (H) below 30% under normal use 
conditions.   
3. 
3. 
3. 
6.22 
6.33.1 
Mandatory
•  Do not turn on the power before attaching the front cover.   
When storing inside the cabinet and using with the front cover removed, always close the 
cabinet doors first and then turn power on. If the power is turned on with the front cover or 
the cabinet doors open, it may result in electric shock.   
•  Make sure that operation signals are off before resetting the inverter after malfunction.   
If the inverter is reset before turning off the operating signal, the motor may restart 
suddenly causing injury.   
•  Provide cranes and hoists with sufficient circuit protection such as mechanical braking.   
Without sufficient circuit protection, the resulting insufficient motor torque during tuning 
could create a risk of machine stalling/falling.   
3. 
10. 
3. 
6.22 
        Caution 
Reference 
Mandatory
•  Observe all permissible operating ranges of motors and mechanical equipment. (Refer to 
the motor's instruction manual)   
Not observing these ranges may result in injury.   
3. 
When sequence for restart after a momentary failure is selected   
        Caution 
Reference 
Mandatory
•  Stand clear of motors and mechanical equipment.   
If the motor stops due to a momentary power failure, the equipment will start suddenly 
when power is restored.   
This could result in unexpected injury.   
•  Attach cautions about sudden restart after a momentary power failure on inverters, motors 
and equipment for prevention of accidents in advance.   
5.18.1 
When retry function is selected 
        Caution 
Reference 
Mandatory
•  Stand clear of motors and equipment.   
If the motor and equipment stop when the alarm is given, selection of the retry function will 
restart them suddenly after the specified time has elapsed and alarm condition has 
disappeared. This could result in unexpected injury. 
•  To prevent accidents, stick caution notices that the inverter has a retry function to the 
inverter, the motor and the machine.   
6.14.1