Toshiba VF-AS1 ユーザーズマニュアル

ページ / 326
!
  E6581301 
I
Maintenance and inspection 
        Warning 
Reference 
Prohibited
•  Never replace any part by yourself.   
This could be a cause of electric shock, fire and bodily injury. To replace parts, call the local 
sales agency.   
14.2 
Mandatory
•  The equipment must be inspected every day.   
If the equipment is not inspected and maintained, errors and malfunctions may not be 
discovered which could lead to accidents.   
•  Before inspection, perform the following steps.   
(1) Turn off all input power to the inverter.   
(2) Wait at least 15 minutes and check to make sure that the charge lamp is no longer lit.   
(3) Use a tester that can measure DC voltage 800VDC or more, and check to make sure 
that the voltage to the DC main circuits (between PA/+ and PC/-) is 45V or less.   
If inspection is performed without performing these steps first, it could lead to electric 
shock.   
14. 
14. 
14.2 
Disposal 
        Caution 
Reference 
Mandatory
•  If you throw away the inverter, have it done by a specialist in industry waste disposal*.   
If you throw away the inverter by yourself, this can result in explosion of capacitor or 
produce noxious gases, resulting in injury.   
(*) Persons who specialize in the processing of waste and known as “industrial waste product 
collectors and transporters” or “industrial waste disposal persons.” If the collection, 
transport and disposal of industrial waste is done by someone who is not licensed for that 
job, it is a punishable violation of the law. (Laws in regard to cleaning and processing of 
waste materials)   
16. 
Attach caution labels 
Shown here are examples of caution labels to prevent, in advance, accidents in relation to inverters, motors and 
other equipment.   
If the inverter has been programmed for auto-restart function after momentary power failure or retry function, place 
caution labels in a place where they can be easily seen and read.   
If  the  inverter  has  been  programmed  for  restart 
sequence  of  momentary  power  failure,  place 
caution labels in a place where they can be easily 
seen and read. 
(Example of caution label) 
If the retry function has been selected, place 
caution labels in a location where they can be 
easily seen and read.   
(Example of caution label) 
Caution
(Functions programmed for restart) 
Caution
(Functions programmed for retry) 
Do not go near motors and equipment.   
Motors and equipment that have stopped 
temporarily after momentary power failure 
will restart suddenly after recovery.   
Do not go near motors and equipment. 
Motors and equipment that have stopped 
temporarily after an alarm will restart 
suddenly after the specified time has elapsed 
and alarm condition has disappeared.