Osburn Stoves by SB I 2200 ユーザーズマニュアル

ページ / 25
 
6
 
1.4 
Manufactured  (Mobile) Home Installations – Additional Requirements
 
 
1.  The stove must be bolted to the floor (secure the unit by prying out the two plastic plugs in the 
pedestal, and installing the two 3/8" x 3-1/2" (9.8mm x 88.9mm) lag bolts through the holes 
provided). 
2. The 
unit 
must
 be provided with outside combustion air. 
3.  Clearance from the top of stove to an unprotected ceiling should be a minimum of  
      52” (1321mm). 
 
Note: For manufactured home installations in the USA, the stove must be grounded to the frame of 
the home using a # 8 ground wire with approved terminations and star lock washers. 
 
C
AUTION
T
HE 
S
TRUCTURAL 
I
NTEGRITY 
O
T
HE 
M
ANUFACTURED 
H
OME 
F
LOOR
, W
ALL
, C
EILING 
R
OOF 
M
UST 
B
M
AINTAINED
C
AUTION
:
  
D
N
OT 
I
NSTALL 
I
A S
LEEPING 
R
OOM
. 
 
1.5 Chimney 
System
 
 
1.5.1 Definitions
 
 
For clarity, the following definitions should be used with respect to these instructions: 
chimney system
 consists of the 
connector
 off the top of the stove, and a 
chimney
, which joins to the 
connector and terminates outside the building envelope. 
chimney
 can be a 
masonry chimney
 (of masonry construction with an inside liner), or a 
factory 
built chimney.
  
factory built chimney 
can be a 
double walled chimney
 (two concentric pipes with insulation 
sometimes referred to as an insulated 
solid pack
, or an 
air cooled chimney
 (three concentric pipes, 
with insulation between the first and second pipes, and air between the second and third pipes). 
single walled
 connector is a single pipe. 
double walled
 connector has two concentric pipes, no insulation, and is an 
air cooled
 connector.