Synchronous Data Refresh
Section 5-4
Synchronous Data
Note
(1) Synchronous data for Coordinator Modules is fixed to general-purpose
(ladder execution results) data.
(2) If there is no synchronous data to be sent, select no data for Select Syn-
chronous Data in the System Setup to shorten the synchronous data
transfer time.
(3) Auxiliary Area data is transferred when input and output refresh method
is set to Immediate refresh and the synchronous data is set to an analog
input or analog output value in the System Setup.
5-4-3
Synchronous Data Link Bit Area
+0
+1
+2
+3
Normal (via Ladder)
Counter 1 values 
Counter 2 values
Pulse output 1
Pulse output 2
Analog input
Analog output 1
Analog output 2
Inner I/O input
(Built-in input)
4 words of data transferred for each Module
System Setup
Select Synchronous 
Data 
Set in upper  
2 words
Example: 4 words of data sent 
by Motion Control Module #1
Counter 1 values
Pulse output 1
Transfer
System Setup
Select Synchronous 
Data
Set in lower 
2 words
Above example: Motion Control 
Module #1 sends its high-speed 
counter 1 PV and pulse output 1 PV 
as the synchronous data link bits.
Synchronous Data 
Link Bit Areas in 
Coordinator and 
Motion Control 
Modules
Word 
address 
(See note 
1.)
Bits
Method for selecting type of synchronous data
Sent from Coordina-
tor Module
CIO 0200
00 to 15
Fixed to general-purpose data (e.g., ladder execution results)
CIO 0201
00 to 15
CIO 0202
00 to 15
Fixed to general-purpose data (e.g., ladder execution results)
CIO 0203
00 to 15
Sent from Motion 
Control Module #1
CIO 0204
00 to 15
Set using upper 2 words of Select Synchronous Data in the System 
Setup for Motion Control Module #1.
CIO 0205
00 to 15
CIO 0206
00 to 15
Set using lower 2 words of Select Synchronous Data in the System 
Setup for Motion Control Module #1.
CIO 0207
00 to 15
Sent from Motion 
Control Module #2
CIO 0208
00 to 15
Set using upper 2 words of Select Synchronous Data in the System 
Setup for Motion Control Module #2.
CIO 0209
00 to 15
CIO 0210
00 to 15
Set using lower 2 words of Select Synchronous Data in the System 
Setup for Motion Control Module #2.
CIO 0211
00 to 15
Sent from Motion 
Control Module #3
CIO 0212
00 to 15
Set using upper 2 words of Select Synchronous Data in the System 
Setup for Motion Control Module #3.
CIO 0213
00 to 15
CIO 0214
00 to 15
Set using lower 2 words of Select Synchronous Data in the System 
Setup for Motion Control Module #3.
CIO 0215
00 to 15