Omron FQM1-CM001 ユーザーズマニュアル

ページ / 414
170
Pulse Outputs
Section 7-6
7-6-5
Applicable Instructions
The following seven instructions can be used to control pulse outputs. The
relationship between the instruction and the types of pulse output that is pos-
sible is also listed in the following table.
Instructions Ineffective 
during Pulse Output
Once pulse output has been started by an instruction, the output cannot
always be changed with an instruction. Refer to 7-6-15 Pulse Output Starting
Conditions
 f
or details on the allowed combinations of pulse output instruc-
tions.
Instruction
Control
Positioning (Independent Mode)
Speed Control (Continuous 
Mode)
No 
acceleration/ 
deceleration, 
single-phase 
output
Acceleration/deceleration, 
single-phase output
No 
acceleration/ 
deceleration, 
single-phase 
output
Acceleration/
deceleration, 
single-phase 
output
No trapezoid, 
acceleration 
and 
deceleration
Trapezoid, 
separate 
acceleration and 
deceleration rates
PULS(886)
Sets number of out-
put pulses or abso-
lute position.
OK
OK
No
No
No
SPED(885)
Controls pulse out-
put without acceler-
ation or 
deceleration (num-
ber of pulses set 
with PULS(886) for 
positioning).
OK
No
No
OK
No
ACC(888)
Controls pulse out-
put with same 
acceleration and 
deceleration with-
out trapezoid (num-
ber of pulses set 
with PULS(886) for 
positioning).
No
OK
No
No
OK
PULS(886) 
for Elec-
tronic Cam
Sets absolute posi-
tion or frequency 
and outputs pulses.
OK
No
No
No
No
PLS2(887)
Controls pulse out-
put with different 
acceleration and 
deceleration with 
trapezoid (number 
of pulses is also set 
using PLS2(887)).
No
No
OK
No
No
INI(880)
Stops pulse output.
OK
OK
OK
OK
OK
PRV(881)
Reads the current 
PV for pulse output.
OK
OK
OK
OK
OK