Installation
P/N 81-CO2MAN-001
4-45
September 2013
Figure 4-35.  Lever and Pressure Operated Control Heads
4-5
AUXILIARY COMPONENTS
4-5.1
Pressure Operated Switches
Pressure operated switches must be connected to the pilot piping or discharge manifolds as 
shown in Figure 4-36 and Figure 4-37. The preferred mounting position is upright. Both the 
standard and explosion-proof pressure switches have 1/2-inch NPT pressure inlets to connect 
to the piping. The electrical connections are either 1/2-inch conduit knockouts or 1-inch NPT 
fittings. The minimum operating pressure required is 50 PSI. 