Power, electrical, and controls  27 
Capacities 
HP POD 20c capacity limitations 
The capacity limitations for the HP POD 20c are separated into two categories: electrical power and 
mechanical cooling capacities. Both of these categories are interdependent and must be considered in 
conjunction with the overall customer requirements. 
 
Electrical and mechanical cooling capacities 
 
Feature 
Specification 
Critical IT electrical 
connections 
2 x 320 A feeders at 380-415 VAC WYE, 3-Phase, 
4-wire, with equipment grounding conductors 5.1 x 
10.2 cm (2 x 4 in) conduit fittings per feeder provided 
Critical IT power 
capacity 
 
Non-redundant—263-288 kW 
 
2N Redundant—132-144 kW 
Mechanical cooling 
electrical connections 
Not applicable 
Power for the cooling system fans comes from the 
critical IT power feeds. 
Mechanical cooling 
capacity 
 
Non-redundant—300 kW 
 
N+1 Redundant—250 kW 
 
 
 
 
Power feeders 
  
 
IMPORTANT:
  A licensed electrician must connect the power according to all local and national 
electrical codes, and must comply with manufacturer specifications. 
  
The HP POD 20c has two power feeder couplings that provide the entrance for power to the POD. The power 
feeders route into the top of each electrical panel on the end of the HP POD 20c.