HP Performance Optimized Data Center (POD) 20cp ユーザーズマニュアル

ページ / 86
 
Power, electrical, and controls  29 
Front view shown 
 
 
Feature 
Specification 
Number of busways 
Frequency 
50-60 Hz 
Amps (per busway) 
200 A 
Voltage (per busway) 
380-415 V 
Grounding 
Copper 
Busway conductors 
3-phase + neutral + equipment ground 
 
 
Panel schedules 
The panel schedule for each electrical panel is permanently affixed to the inside cabinet door of each 
electrical panel. 
 
Wire color code 
  
 
IMPORTANT:
  The use of UL-approved colored tape over another color of wire is only acceptable 
on wire sizes #2 and larger. 
  
220-240 V wiring system—Power required for the transformer in control cabinets and convenience outlet 
 
Wire color 
Description 
Brown 
Single-phase current carrying conductor 
White 
Blue 
Green and yellow 
 
Equipment grounding conductor 
 
Bonding conductor 
 
Earth ground 
 
 
 
380-415 V wiring system—Critical IT power feeds and main power feeds