Modbus Parameters
Page 103
Parameter Name
Modbus Address
Access
Values
(Dec)
(Hex)
Proportional Band
Integral Time 
Constant
4314
0x10DA
R/W
0.0 to 5999 Seconds
Derivative Time 
Constant
4315
0x10DB
R/W
0.0 to 5999 Seconds
Bias
4316
0x10DC
R/W
For single control 0 to 100.
For Dual control -100 to 100
Overlap/Deadband
4317
0x10DD
R/W
-100 to 100
On/Off Differential
4320
0x10E0
R/W
0.1 to 100
Primary Power 
Upper limit
4321
0x10E1
R/W
10 to 100% Can not be made smaller than Primary 
Lower limit + 10
Heat/Primary Power 
Lower limit
4322
0x10E2
R/W
0 to 90% Can not be made larger than Heat/Primary 
Upper limit – 10
Cool/Secondary 
Upper Power limit
4323
0x10E3
R/W
10 to 100% Can not be made smaller than 
Cool/Secondary Lower limit + 10
Cool/Secondary 
Power Lower limit
4324
0x10E4
R/W
0 to 90% Can not be made larger than 
Cool/Secondary Upper limit – 10
Pre-Tune 
Engage/disengage
4325
0x10E5
R/W
Value
Pre-Tune Engage/disengage
0
Pre-Tune OFF
1
Run Pre-Tune
Self-Tune 
Engage/disengage
4326
0x10E6
R/W
Value
Self-Tune Engage/disengage
0
Self-Tune OFF
1
Self-Tune ON
Loop Alarm Type
4327
0x10E7
R/W
Value
Loop Alarm Type
1
Timed
2
Automatic (2x Integral Time)
Loop Alarm Time
4328
0x10E8
R/W
1 to 5999 Seconds after output saturation
Primary Power
4329
0x10E9
RO
The current primary power (0 to 100%)
Secondary Power
4330
0x10EA
RO
The current secondary power (0 to 100%)
Combined Power
4331
0x10EB
RO
The current combined PID power (-100 to 100%)
Pre-Tune Status
4332
0x10EC
RO
Value
Pre-Tune Status
0
Inactive
1
Active
Self-Tune Status
4333
0x10ED
RO
Value
Self-Tune Status
0
Inactive
1
Active
Loop Alarm status
4334
0x10EE
RO
Value
Loop Alarm Status
0
Inactive
1
Active
Input Failure Preset 
Power
4335
0x10EF
R/W
Power output required if input signal is lost 0 to 100% 
(-100% to 100% for dual control).
Auto Pre-tune
4336
0x10F0
R/W
Value
Auto Pre-Tune
0
Disabled
1
Enabled