DCP200 Profile Controller & Recorder - Product Manual
Page 104
Modbus Parameters
51-52-25-150, Issue 1 – April 2009
Alarm parameters
Parameter Name
Modbus Address
Access
Values
(Dec)
(Hex)
Alarm 1 Type
6144
0x1800
R/W
Value
Alarm 1 Type
0
Process High Alarm
1
Process Low Alarm
2
Deviation Alarm (SP-PV)
3
Band Alarm
4
Loop Alarm
5
Input/Sensor Break Alarm
6
Auxiliary Input A Break Alarm
7
Auxiliary Input B Break Alarm
Alarm 1 Value
6145
0x1801
R/W
Limited by the input range maximum and minimum for 
Alarm types 0 and 1. Limited by the input span for 
alarm types 2 and 3. Not used for alarms 4 to 7.
Alarm 1 Hysteresis
6146
0x1802
R/W
Limited by the input span
Alarm 1 Inhibit 
Enable/disable
6147
0x1803
R/W
Value
Alarm 1 Inhibit Enable
0
Disabled
1
Enabled
Alarm 1 Status
6148
0x1804
RO
Value
Alarm 1 Status
0
Inactive
1
Active
Alarm 1 Inhibit 
Status
6149
0x1805
RO
Value
Alarm 1 Inhibit Status
0
Not Inhibited
1
Inhibited
Alarm 2 Type
6160
0x1810
R/W
Value
Alarm 2 Type
0
Process High Alarm
1
Process Low Alarm
2
Deviation Alarm (SP-PV)
3
Band Alarm
4
Loop Alarm
5
Input/Sensor Break Alarm
6
Auxiliary Input A Break Alarm
7
Auxiliary Input B Break Alarm
Alarm 2 Value
6161
0x1811
R/W
Limited by the input range maximum and minimum for 
Alarm types 0 and 1. Limited by the input span for 
alarm types 2 and 3. Not used for alarms 4 to 7.
Alarm 2 Hysteresis
6162
0x1812
R/W
Limited by the input span
Alarm 2 Inhibit 
Enable/disable
6163
0x1813
R/W
Value
Alarm 2 Inhibit Enable
0
Disabled
1
Enabled
Alarm 2 Status
6164
0x1814
RO
Value
Alarm 2 Status
0
Inactive
1
Active
Alarm 2 Inhibit 
Status
6165
0x1815
RO
Value
Alarm 2 Inhibit Status
0
Not Inhibited