DCP200 Profile Controller & Recorder - Product Manual
51-52-25-150, Issue 1 – April 2009
Modbus Parameters
Page 119
Segment Data
The Segment Data is included in the command message when creating, editing or inserting 
segments (see above). It is provided in two parts (Segment Info A and B).
The meaning of the data contained in Segment Info A and B depends on the type of segment 
it relates to. Null is shown for unused data, these data values should be set to zero when 
writing the segment data.
Segment 
Type
Segment Info
Description
A
B
Ramp Time
Time
Target setpoint
Ramp to the target setpoint “B” in the time “A”
Ramp Rate
Ramp rate
Target setpoint
Ramp to the target setpoint “B” at the ramp rate “A”
Step
Null
Target setpoint
Step to a target setpoint “B”
Dwell
Dwell time
Null
Stay at the current setpoint for a period of time “A”
Hold
0 = Operator 
Null
Wait for the operator to release the hold
1 = Time of day
Start Time
Wait until time of the day “B” in seconds since 
midnight. (recorder only).
2 = Aux A digital 
input
Null
Wait for digital input A signal
3 = Aux B digital 
input
Null
Wait for digital input B signal
Loop
Number of times to 
repeat 1 to 9999
Segment number
Loop to the specified segment number “B” from this 
point. Repeat this “A” times. Only segments below 
the current segment can be entered. Two loops 
must not cross each other.
Join
Null
Profile number
On completion of this profile jump run profile “B”
End
0 = Control off
Null
Turn off all control outputs.
1 = Maintain profile 
setpoint
Null
Stay at the final setpoint of the profile
2 = Use controller 
setpoint 
Null
Use the active controller setpoint.
Repeat 
Sequence 
Then End
0 = Outputs off
Number of times to
repeat sequence
Repeat the profile sequence number “B” times, 
then turn off the control outputs
1 = Maintain profile 
setpoint
Repeat the profile sequence number “B” times, 
then hold the last profile setpoint.
2 =  Use controller 
setpoint 
Repeat the profile sequence number “B” times, 
then use the active controller setpoint.
The instrument replies to this message with an Edit Response Message.
Deleting Profiles
An individual profile can be deleted, or all profiles can be cleared with a single message. 
Deleting a profile removes the header of the specified profile and any segments associated 
with it. Delete all profiles wipes all profiles and segments from the instrument.
Delete Profiles - Request (to instrument)
Field Name
Data
Comments
(Dec)
(Hex)
Unit Address
A/R
A/R
The ID address of the instrument.
Function Code
23
17
Requires the multi read/write function
Read Start Address High Byte
32
20
Read Start Address Low Byte
06
06
Read Quantity Of Registers High
00
00
Read Quantity Of Registers Low
01
01