DCP200 Profile Controller & Recorder - Product Manual
Page 120
Modbus Parameters
51-52-25-150, Issue 1 – April 2009
Delete Profiles - Request (to instrument)
Field Name
Data
Comments
(Dec)
(Hex)
Write Start Address High
32
20
Write Start Address Low
06
06
Write Quantity Of Registers High
00
00
Write Quantity Of Registers Low
02 or 01
02 or 01
Delete A Profile (DP) = 02dec / 0x02hex
Delete All Profiles (DA) = 01dec / 0x01hex
Byte Count
04 or 02
04 or 02
Delete A Profile (DP) = 04dec / 0x04hex
Delete All Profiles (DA) = 02dec / 0x02hex
Command Code High Byte
68
44
Command Code Low Byte
80 or 65
50 or 41
Delete A Profile (DP) = 80dec / 0x50hex
Delete All Profiles (DA) = 65dec / 0x41hex
Profile Number High Byte
A/R
A/R
Note: The profile number is not included 
in the message when deleting all 
profiles.
Profile Number Low Byte
A/R
A/R
CRC High Byte
A/R
A/R
CRC Low Byte
A/R
A/R
The instrument replies to this message with an Edit Response Message.
Delete A Segment
The delete segment command deletes the specified segment from the specified profile. The 
following segments are moved up one place in the profile (e.g. if segment 6 is deleted 
segment 7 now becomes segment 6).
Delete A Segment - Request (to instrument)
Field Name
Data
Comments
(Dec)
(Hex)
Unit Address
A/R
A/R
The ID address of the instrument
Function Code
23
17
Requires the multi read/write function
Read Start Address High Byte
32
20
Read Start Address Low Byte
06
06
Read Quantity Of Registers High
00
00
Read Quantity Of Registers Low
01
01
Write Start Address High
32
20
Write Start Address Low
06
06
Write Quantity Of Registers High
00
00
Write Quantity Of Registers Low
03
03
Byte Count
06
06
Command Code High Byte
68
44
Command Code Low Byte
83
53
Profile Number High Byte
A/R
A/R
Profile Number Low Byte
A/R
A/R
Segment Number High Byte
A/R
A/R
Segment Number Low Byte
A/R
A/R
CRC High Byte
A/R
A/R
CRC Low Byte
A/R
A/R
The instrument replies to this message with an Edit Response Message.