DCP200 Profile Controller & Recorder - Product Manual
Page 122
Modbus Parameters
51-52-25-150, Issue 1 – April 2009
Command Response Data
The data contained in the Edit Response Message returned after each profile or segment 
edit message is shown below. The data seen can be an error code, the number of unused 
segments or the profile number following a successful profile header creation/edit.
The error code shown will be as appropriate for the request message and instrument status.
Command Response Name
Two Byte Response
Description
Low Byte
High Byte
Profile Number
A/R
A/R
The number of the profile created or edited
Segments Remaining
A/R
A/R
The number of unused segments remaining
Command Successfully
0x4F
0x4B
The command requested executed without error
Command Not Recognized 
0xFF
0xFF
The command is not recognized
Profile Number Invalid
0xF0
0x00
The profile number specified is not available. 
Profile Name Invalid
0xF0
0x01
The profile name/characters are not valid
Start Signal Invalid
0xF0
0x02
The start signal is not recognized
Start Time Invalid
0xF0
0x03
The specified time is not within range
Start Day Invalid
0xF0
0x04
The specified day is not recognized
Starting Setpoint Invalid
0xF0
0x05
The specified starting setpoint is not recognized
Profile Recovery Invalid
0xF0
0x06
The profile recovery is not recognized
Recovery Time Invalid
0xF0
0x07
The recovery time is not within limits
Abort Action Invalid
0xF0
0x08
The abort action is not recognized
Profile Cycles Invalid
0xF0
0x09
The number of profile cycles is not within limits
Segment Number Invalid
0xF0
0x0A
The segment number is not valid for this profile
Segment Type Invalid
0xF0
0x0B
The segment type is not recognized
Segment Info A Invalid
0xF0
0x0C
The segment information A not valid for segment 
type defined
Segment Info B Invalid
0xF0
0x0D
The segment information B is not valid for the 
segment type defined 
Auto Hold Type Invalid
0xF0
0x0E
The auto hold type is not recognized
Auto Hold Value Invalid
0xF0
0x0F
The auto hold value is not within input span
Events Value Invalid
0xF0
0x10
The events are not within range
No Segments Remaining
0xF0
0x11
There are no more segments available
Write Length Invalid
0xF0
0x12
The number of parameters to be written are invalid 
for the function requested
Segment Setpoint Clamped
0xF0
0x13
The setpoint value entered was out of bounds. It 
has been clamped within the units setpoint limits.
Read A Profile Header
Read A Profile Header - Request (to instrument)
Field Name
Data
Comments
(Dec)
(Hex)
Unit Address
A/R
A/R
The ID address of the instrument
Function Code
23
17
Requires the multi read/write function
Read Start Address High Byte
32
20
Read Start Address Low Byte
06
06
Read Quantity Of Registers High Byte
00
00
Read Quantity Of Registers Low Byte
18
12
Write Start Address High Byte
32
20
Write Start Address Low Byte
06
06