DCP200 Profile Controller & Recorder - Product Manual
Page 172
PC Software
51-52-25-150, Issue 1 – April 2009
Edit Modbus Settings
The Edit Modbus Settings tab configures the 
connection between the Ethernet module and the 
instrument’s microprocessor. These settings 
MUST match with the settings in the instruments 
Communications Configuration menu. A faster 
baud rate can be used if large amounts of data 
are to be sent between the instrument and the 
master, but in most cases, it is recommended that 
the default settings are used.
Defaults:
Baud Rate
9600
Data Bits
Eight
Stop Bits
One
Parity
None
Fixing An IP Address
If your instrument cannot be found using the “Search Network” button, the IP address can be 
set from the Set IP Address option on the software’s System menu.
Enter it’s MAC Address* and the new IP 
Address (use 0.0.0.0 for automatic addressing) 
then press okay.
*If your instruments 12 digit MAC Address isn’t 
know, it can be found on a label attached to the 
RJ45 connector of it’s Ethernet module.