Honeywell VCR DCP200 ユーザーズマニュアル

ページ / 184
DCP200 Profile Controller & Recorder - Product Manual
51-52-25-150, Issue 1 – April 2009
Specifications
Page 173
17 Appendix 2 - Specifications
Universal Process Input
General Input Specifications
Input Sample Rate:
Ten samples per second.
Digital Input Filter 
time constant
0.0 (OFF), 0.5 to 100.0 seconds in 0.5 second increments.
Input Resolution:
Always four times better than display resolution. 16 bit ADC.
Supply Voltage 
Influence:
Negligible effect on readings within the specified supply voltage 
tolerances.
Relative Humidity 
Influence:
Negligible effect on readings within the specified humidity tolerance.
Temperature 
Stability:
0.01% of span/C change in ambient temperature.
Input Impedance:
V DC: 
47KΩ
mA DC:
Other ranges: 
Greater than 10M resistive
Isolation: 
Isolated from all outputs (except SSR Drivers) at 240V AC
PV Offset:
Adjustable input span. +ve values are added to Process Variable, -ve 
values are subtracted from Process Variable
PV Display:
Displays process variable up to 5% over and 5% under span.
Thermocouple Input
Thermocouple Types & Ranges
Sensor 
Type
Range in 
Range in F
Sensor 
Type
Range in 
Range in F
B
100 to 1824°C
211 to 3315°F
L
0 to 762°C
32 to °F
C
0 to 2315°C
32 to 4199°F
N
0 to 1399°C
32 to 2551°F
D
0 to 2320°C
32 to 4208°F
PtRh20%:
PtRh40%
0 to 1850°C
32 to 3362°F
E
-240 to 1000°C
-400 to 1832°F
R
0 to 1759°C
32 to 3198°F
J (default) -200 to 1200°C
-328 to 2192°F
S
0 to 1762°C
32 to 3204°F
K
-240 to 1373°C
-400 to 2503°F
T
-240 to 400°C
-400 to 752°F
Note:
Defaults to °F for USA units. Defaults to °C for non-USA units.
The Scale Range Upper Limit and Scale Range Lower Limit parameters, can be used to 
restrict range. An optional decimal place can be displayed up to 999.9°C/F