Page 175
DC Linear Input
DC Linear Types & Ranges
Input 
Type
Ranges
Input 
Type
Ranges
mA DC 
0 to 20mA
4 to 20mA
V DC
0 to 5V
1 to 5V
mV DC
0 to 50mV
10 to 50mV
2 to 10V
0 to 10V
DC Linear Performance
Display Scaling:
Scalable up to –9999 to 10000 for any DC Linear input type.
Minimum Span:
100 display units.
Decimal Point 
Display:
Decimal point selectable from 0 to 3 places, but limits to 5 display digits 
(e.g. values > 99.9 have no more than 2 decimal places).
DC Input Multi-Point 
Linearization:
Up to 15 scaling values can be defined anywhere between 0.1 and 100% 
of input.
Measurement 
Accuracy:
0.1% of span 1LSD.
Maximum Overload:
1A on mA input terminals, 30V on voltage input terminals.
Sensor Break 
Protection:
Applicable for 4 to 20mA, 1 to 5V and 2 to 10V ranges only.
Break detected within two seconds. Process Control outputs go to the 
pre-set power value. Low and Senor Break Alarms operate.
Auxiliary Inputs
Auxiliary Input Types & Ranges
Input 
Type
Ranges – Auxiliary Input A
Input 
Type
Ranges – Auxiliary Input B
mA DC 
0 to 20mA
4 to 20mA
mA DC 
0 to 20mA
4 to 20mA
V DC
0 to 5V
1 to 5V
V DC
0 to 5V
1 to 5V
2 to 10V
0 to 10V
2 to 10V
0 to 10V
mV DC
0 to 100mV
10 to 50mV
Pot
2KΩ or higher
Auxiliary Input Performance
Input Sampling rate:
4 per second.
Input Resolution:
16 bit ADC.
Auxiliary Input 
Scaling:
Scalable as a Remote Setpoint (RSP) input between –9999 and 10000, 
constrained by the Setpoint Limits.
Measurement 
Accuracy:
0.25% of input span 1 LSD.