Honeywell VCR DCP200 ユーザーズマニュアル

ページ / 184
DCP200 Profile Controller & Recorder - Product Manual
Page 34
Electrical Installation
51-52-25-150, Issue 1 – April 2009
Option Slot 3 – Dual SSR Driver Output Module
If option slot 3 is fitted with a dual SSR driver output module, make connections as 
illustrated. The solid-state relay drivers are a 0-10V DC signal, load impedance must be no 
less than 500 ohms. SSR driver outputs are not isolated from the signal input or other SSR 
driver outputs.
Figure 28.
Option Slot 3 – Dual SSR Driver Module
Option Slot 3 - Triac Output Module
If option slot 3 is fitted with a Triac output module, make connections as shown. This output 
is rated at 0.01 to 1 amp @ 280V AC 50/60Hz. A snubber should be fitted across inductive 
loads to ensure reliable switch off the Triac.
Figure 29.
Option Slot 3 - Triac Module
Option Slot 3 - Linear Voltage or mADC Output module
If option slot 3 is fitted with a DC linear output module, make connections as illustrated.
Figure 30.
Option Slot 3 - Linear Voltage & mADC module
10
11
_
12
+
10
11

10
11
-
OUTPUT 3A
-
OUTPUT 3B
12
+
COMMON