DCP200 Profile Controller & Recorder - Product Manual
51-52-25-150, Issue 1 – April 2009
Configuration & Use
Page 49
Input Configuration Sub-Menu
Table 9. Input Configuration Sub-Menu Screens
Input Configuration:
Process Variable Input 
Type
From various Thermocouple, RTD and Linear inputs. - see 
specifications section for full details of input types available.
Engineering Units
Select display units from: °C; °F; °K; bar; %; %RH; pH; psi or none.
Decimal Point Position
Sets the maximum display resolution to 0; 1; 2 or 3 decimal places. 
Temperature inputs are limited to 0 or 1 place. Numbers >99.999 
never display more than 2 dec places, >999.99 never display more 
than 1 dec place and >99999 always display without a decimal place.
Multi-Point Scaling 
Enable
Enables or disables Linear Input Multi-Point Scaling. This feature 
allows up to 15 point linearization of mA or V DC input signals.
Scale Range Lower 
Limit
For Temperature inputs, Upper & Lower Limits set the usable span. 
Min span = 100 units, max span = range limits - see specs. For 
Linear inputs, Upper & Lower Limits define the values shown (-1999 
to 9999) when input is at minimum and maximum values. Min span = 
100 units. If Multi-Point Scaling is enabled, up to 15 breakpoints* can 
scale input vs. displayed value between the linear input scale limits.
*A breakpoint set at 100% input ends the sequence. 
Multi-Point Scale 
Point(s)
Scale Range Upper 
Limit
w
CJC Enable/Disable
Enables/disables internal Thermocouple Cold Junction 
Compensation. If disabled, external compensation will be required for 
thermocouples. The default value is Enabled.
Process Variable Offset
Trims the measured process value. +Ve values add to, –Ve values 
subtract from measured input. 
Caution:
A value other than zero 
alters the apparent calibration of the instrument. Use with care!
Input Filter Time
Removes unwanted signal noise. Adjustable from 0.0 (OFF) to 100.0 
seconds or OFF (default = 2s). 
Caution:
Too large a value will cause 
slow response to changes in the process. Use with care!
Auxiliary Input Type
Sets the type of signal to be connected to the auxiliary inputs (if 
fitted). From: 0-10V; 2-10V; 0-5V; 1-5V, 0-20mA or 4-20mA DC.
Auxiliary input B also supports >2K Potentiometer and 0-100mV.
Auxiliary Input Scaling 
Lower Limit
Scales the displayed a value (-9999 to 10000) when an auxiliary 
input is at or below it’s lower limit (e.g. 4mA for a 4-20mA signal).
Auxiliary Input Scaling 
Upper Limit
Scales the displayed a value (-9999 to 10000) when an auxiliary 
input is at or above it’s lower limit (e.g. 20mA for a 4-20mA signal).
Auxiliary Input Offset
Trims the displayed a value for auxiliary input A or B. +Ve values are 
added to, –Ve values subtracted from the measured auxiliary input.
Calibration Reminder 
Enable/Disable
Enables or disables the display of Calibration Reminder at start-up 
(repeated daily thereafter), if the due date has passed – Available on 
the Recorder version only
Calibration Reminder 
Due Date
Sets the due date for the Calibration Reminder - Available on the 
Recorder version only