Control Configuration Sub-Menu
Table 10. Control Configuration Sub-Menu Screens
Control Configuration:
Control Enable/Disable
Sets the method used to enable/disable the control output(s). From: 
Enabled (always); Disabled (always); Enable/Disable via Digital Input 
A or B, or Operator Selectable (allows control output(s) to be turned 
off from Operation Mode
). 
Caution:
The instrument is not able to 
control the process when control is disabled. The Output Power 
Lower Limit parameters are also ignored. Use with care!
Auto/Manual Mode 
Access
Sets the method used to select Automatic or Manual Control. From: 
Automatic (always); Manual (always); Select via Digital Input A or B, 
or Operator Selectable (allows automatic or manual control to be 
selected from Operation Mode
). 
Caution:
In Manual Mode, the user 
must monitor and alter power to correctly control the process (0 to 
100% or -100 to +100% for dual control). Manual power is not 
restricted by the Output Power Limit parameters. Use with care!
Control Type
Set to Single Control for Primary control only (e.g. Heating or Cooling 
only) or to Dual for Primary and Secondary Control outputs (e.g. 
Heating & Cooling).
Primary Control Action
Set the Primary Control Output for Reverse or Direct Action. Reverse 
action applies more primary power as the process falls further below 
setpoint (e.g. heating applications). Direct action applies more 
primary power as the process rises further above setpoint (e.g. 
cooling applications).
If Dual Control is used, the secondary output action is always
opposite to the Primary action.
Control Status
Displays the current Process Variable and Setpoint values to aid 
manual tuning – This screen is Read Only.
Power Output Level
Displays the current Primary and Secondary control power levels 
(each 0 to 100%) to aid manual tuning – This screen is Read Only.
Primary Proportional 
Band
Sets the width of the Primary Proportional Band between 0.5% and 
999.9%, or select On-Off control. – This screen is Read Only during 
automatic tuning.
Secondary Proportional 
Band
Sets the width of the Secondary Proportional Band between 0.5% 
and 999.9%, or select On-Off control. – This screen is Read Only 
during automatic tuning.
Integral Time Constant
Sets the Integral Time Constant (Automatic Reset) from 1s to 99min 
59s or OFF. – This screen is Read Only during automatic tuning.
Derivative Time 
Constant
Derivative Time Constant (Rate) from 1s to 99 min 59s or OFF. 
This screen is Read Only during automatic tuning.
Manual Reset (Bias)
Sets the Manual Reset (Proportional Band Bias) from 0-100%
or -100 to +100% for Dual Control.
Overlap / Deadband
Sets the Overlap (+ve values) or Deadband (-ve values) between 
Primary & Secondary Proportional Bands when Dual Control is used.
Primary On-Off 
Differential
Sets the Primary On-Off control hysteresis (deadband) from 0.1 to 
10.0% of Span (centred about setpoint), when Primary On-Off control 
is used.