Honeywell VCR DCP200 ユーザーズマニュアル

ページ / 184
DCP200 Profile Controller & Recorder - Product Manual
Page 54
Configuration & Use
51-52-25-150, Issue 1 – April 2009
Recorder Configuration Sub-Menu
Table 14. Data Recorder Configuration Sub-Menu Screens
Recorder Configuration:
No Recorder Warning
If the Recorder Configuration menu is entered on an instrument 
without this option fitted.
Recording In Progress 
Warning
If recording in progress when Recorder Configuration entered. –
Allows access to the Recording Start/Stop screen only, until the 
recording is stopped
.
Recorder Mode
w
Choose Record Until Memory Used (Stop recording when full) or 
Continuous FIFO (First In - First Out) -
Caution:
A FIFO recording 
will overwrite all previous recordings in memory, starting with the 
oldest data first. Download the previous data to USB memory stick 
before selecting this option.
Recording Sample 
Interval
w
A recording of the selected data will be taken once every Sample 
Interval. From: Every 1; 2; 5; 10; 15; 30 Seconds, or Every 1; 2; 5; 
10; 15; 30 Minutes. Note: Short intervals will reduce the maximum 
possible duration of the recording.
Recorder Trigger 
w
The recording Start/Stop trigger method to be used. From: Operation 
Mode selection; Recorder Menu selection; On Alarm(s); Digital Input 
A or B state; or During Profiles.
Trigger On Alarms
Any from: Alarm – Where is alarms 1 to 5. Any combination of 
these can be set to trigger (TRG) or not (OFF). Any active alarm set 
to TRG will start the instrument recording. Note: Recording will only 
stop if all alarms selected as triggers become inactive.
Values To Record
Any from: Process Variable value; Maximum or Minimum PV (since 
the previous sample was taken); Setpoint; Primary Power or 
Secondary Power. Any combination of these can be set to Record 
(REC) or not (OFF). Note: Recording more parameters will reduce 
the maximum possible duration of the recording.
Alarms & System 
Events To Record
Any from: Alarm Status or Unit turned On/Off. 
Caution:
An alarm 
state change between samples is also recorded. This uses additional 
recorder memory, which may cause the recording to end sooner than 
expected.
Profiler Events To 
Record
Any from:  Profiler Event Status. 
Caution:
A profile event state 
change between samples is also recorded. This uses additional 
recorder memory, which may cause the recording to end sooner than 
expected.
Recorder Status 
Information
Shows if a recording is in progress; the recording mode; memory 
usage per sample; memory remaining and the recording time 
remaining. The time remaining is adjusted for any alarm/events that 
have already occurred, but cannot allow for any future alarms/events