DCP200 Profile Controller & Recorder - Product Manual
Page 56
Configuration & Use
51-52-25-150, Issue 1 – April 2009
Lock Code View
Unlock Codes
To prevent unauthorised entry, some menus are protected by a lock code. These screens 
are indicated by the  symbol before their names in the screen list tables. To enter these 
screens, the correct code must first be entered. The current lock codes can be viewed and 
changed from the Lock Code View Configuration sub-menu.
The default unlock code for all protected menus is 10. For security, users are recommended 
to change these codes. A value between 1 and 9999 can be used, or the lock can be set to 
OFF if no protection is required.
Navigating Lock Code View
Press 
to move forward or 
to move backwards through the screen elements.
Press 
or 
to change the value as required.
Hold down 
and press 
to return to the Main Menu
Scrolling “Help Text” is shown at the bottom of the screens to aid navigation.
Table 17. Lock Code View Sub-Menu Screens
Lock Code View:
Lock Code View 1
Setup Wizard; Configuration Mode and Tuning Menu Lock Codes
(1-9999 or OFF).
Lock Code View 2
Supervisor Mode; USB; Recorder and Profiler Menu Lock Codes 
(1-9999 or OFF) - if fitted/configured.
Lost Lock Codes
The lock codes can be viewed or changed from Configuration Mode. In the event that the 
Configuration Mode lock code itself is forgotten, the instrument can be forced into Lock Code 
View from power-up, where the codes can be checked or set to new values.
Forcing Lock Code View
Power down the instrument.
Re apply the power and hold down 
and 
for more than 5 seconds as the start-up 
splash screen appears. Lock Code View will appear.
Press 
to move forward or 
to move backwards through the screen elements.
Make note of the codes or press 
or 
to change their values if required.
Hold down 
and press 
to return to the Main Menu
Scrolling “Help Text” is shown at the bottom of the screens to aid navigation.