Profile Header Details
Profile Header:  Settings that apply to the chosen profile as a whole
Enter Profile Name
 Up to 16 characters can be used to name each profile
Profile Starting 
Point
 The setpoint value to be used at the beginning of the first segment. 
From: Actual Setpoint or Process Variable value at the time the 
profile starts.
Profile Start 
Trigger
 From: None (profile start is not delayed); After Delay or Day and 
Time (Recorder version only).
Profile Start Time
 The time (hh:mm:ss) when the profile should run. – This applies only 
if Day and Time is the Profile Start Trigger. 
Caution:
Take care not 
to clash with other profiles. A Profile cannot start if another is 
running.
Profile Start Day(s)
 The Day(s) when the profile should run. From: Mon; Tue; Wed; Thu; 
Fri; Sat; Sun; Mon-Fri; Mon-Sat; Sat-Sun or All. – This applies only if 
Day and Time is the Profile Start Trigger.
Profile Start Delay
 The delay time, up to 99:59 (hh:mm), for a profile to begin after the 
start request has been given.
Profile Recovery 
Method
 The power-on action if profile was running at power-down (e.g. after 
a power cut), or following correction of a signal break. From: Control 
outputs off; Restart profile from the beginning; Maintain last profile 
setpoint; Use controller setpoint; Continue profile from where it was 
when power failed.
Profile Recovery 
Time
 The Recovery Method is ignored (the profile continues from where 
power failed), if power off for less than this time.  Max 99:59 
(hh:mm). - Recorder version only.
Profile Abort 
Action
 Action after profile has been forced to stop before its end. From:
Control outputs off; Maintain last profile setpoint or Use controller 
setpoint.
Profile Cycles
 The number of times the program should run each time it is started 
(1-9999 or Infinite).
Profile Segment Details
Profile Segments:  Settings that apply to individual profile segments
Segment Number
 Shows the number of the profile segment being created from 1-255
Segment Type
 Set the segment type from: Ramp Time (time to reach target SP); 
Ramp Rate (rate of change towards target SP); Step (jump to target 
SP), Dwell (keep current SP);  Hold (hold the profile until released); 
Loop (back to a previous segment); Join (join to another profile); 
End (end the profile) or Repeat Sequence Then End (repeat a 
sequence of joined profiles – of which this is the last). A Join, End or 
Repeat Sequence Then End will become the last segment in the 
profile.
Segment Target 
Setpoint
 The setpoint value to be reached by the end of this segment, if the 
segment type is Ramp Time, Ramp Rate or Step.
Segment Ramp 
Time
 The time (hh:mm:ss) to reach the Segment Target Setpoint if the 
segment type is Ramp Time.
Segment Ramp 
Rate
 The rate of change towards the Segment Target Setpoint if the 
segment type is Ramp Rate. The rate can be set from 0.001 to 
9999.9 display units per hour.
Segment Dwell 
Time
 The time (hh:mm:ss) to maintain the current setpoint if the segment 
type is Dwell.