51-52-25-150, Issue 1 – April 2009
Table 19. Automatic Tuning Menus Screens
 Automatic Tuning Menu:
Automatic Tuning Mode 
Unlocking
Enter correct code number to access the Automatic Tuning Menu.
Turns Pre-Tune on/off. Pre-Tune is disabled in On-Off Control Mode; 
if the PV is less than 5% of span from SP; during Profiles or if the 
Setpoint is Ramping.
Pre-Tune Status
Shows the current Pre-Tune status. Active or Inactive.
Self-Tune
Turns Self-Tune on/off. Self-Tune is disabled in On-Off Control 
Mode.
Self-Tune Status
Shows current Self-Tune status. Active or Inactive.
Auto Pre-Tune Enable
Enables/Disables Automatic Pre-Tune. When enabled, this attempts 
to perform a Pre-Tune at every power-up. Normal Pre-Tune 
engagement rules are applied (see Pre-Tune above).
Profiler Setup Menu
Refer to the Profiler Option section of this manual for more details about the profiler features.
Screens marked  will not time-out automatically. They must be completed for a valid profile 
to be created.
Table 20. Profiler Setup Menu Screens
 Profiler Menu:
General
General Profile Configuration:  Settings that apply to all profiles
Profile Run/Hold 
Signal
Selects the method used to Run or Hold a profile. From: Digital Input 
A; Digital Input B or Key Pad Only (using the either the Profile 
Control Menu or an Operation Mode screen).
Profile Abort 
Signal
Selects the method used to force a profile to end prematurely. From: 
Digital Input A; Digital Input B or Key Pad Only (using either the 
Profile Control Menu or an Operation Mode screen).
Control In 
Operation Mode
Enables/disables the ability to control profiles (run, hold or abort) 
from Operation Mode.
Enable Edit While 
Running
Enables/disables the ability to edit profiles whist a profile is running 
(even if selected, the current or next segment of the running profile 
will not change until after the profile is restarted).
Create A Profile
 Creates a new profile. A header is created first, followed by the 
segments – see below. A warning is displayed if the maximum 
number of 64 profiles or 255 segments is exceeded.