Honeywell VCR DCP200 ユーザーズマニュアル

ページ / 184
DCP200 Profile Controller & Recorder - Product Manual
51-52-25-150, Issue 1 – April 2009
Modbus Parameters
Page 85
Parameter Name
Modbus Address
Access
Values
(Dec)
(Hex)
Input Signal Under 
Range Flag
1033
0x0409
RO
Value
Process Input Under Range Status
0
Inactive
1
Active
Input Signal Over 
Range Flag
1034
0x040A
RO
Value
Process Input Over Range Status
0
Inactive
1
Active
Cold Junction 
Compensation 
Enable/disable
1035 
0x040B
R/W
Value
CJC Status
0
Disabled
1
Enabled (default)
Calibration Reminder 
Enable
1048
0x0418
R/W
Value
Calibration Reminder Status
0
Disabled
1
Enabled
Calibration Reminder 
Date
1049
0x0419
R/W
Data Format = ddmmyy where dd = day, mm = month 
and yy = year (e.g. 200308 is 20
th
March 2008)
Calibration Reminder 
Status
1052
0x041C
RO
Value
Calibration Status
0
Calibration OK
1
Calibration Required
Multi-point Scaling 
Enable
1053
0x041D
R/W
Value
Multi-point Scaling Status
0
Disabled
1
Enabled (only if the input type is linear)
Scale Point 1
1054
0x041E
R/W
0.1 to 100.0% 
Display Point 1
1055
0x041F
R/W
Valid between scale range maximum and minimum
Scale Point 2
1056
0x0420
R/W
>Scale point 1 to 100.0%
Display Point 2
1057
0x0421
R/W
Valid between scale range maximum and minimum
Scale Point 3
1058
0x0422
R/W
>Scale point 2 to 100.0%
Display Point 3
1059
0x0423
R/W
Valid between scale range maximum and minimum
Scale Point 4
1060
0x0424
R/W
>Scale point 3 to 100.0%
Display Point 4
1061
0x0425
R/W
Valid between scale range maximum and minimum
Scale Point 5
1062
0x0426
R/W
>Scale point 4 to 100.0%
Display Point 5
1063
0x0427
R/W
Valid between scale range maximum and minimum
Scale Point 6
1064
0x0428
R/W
>Scale point 5 to 100.0%
Display Point 6
1065
0x0429
R/W
Valid between scale range maximum and minimum
Scale Point 7
1066
0x042A
R/W
>Scale point 6 to 100.0%
Display Point 7
1067
0x042B
R/W
Valid between scale range maximum and minimum
Scale Point 8
1068
0x042C
R/W
>Scale point 7 to 100.0%
Display Point 8
1069
0x042D
R/W
Valid between scale range maximum and minimum
Scale Point 9
1070
0x042E
R/W
>Scale point 8 to 100.0%
Display Point 9
1071
0x042F
R/W
Valid between scale range maximum and minimum
Scale Point 10
1072
0x0430
R/W
>Scale point 9 to 100.0%
Display Point 10
1073
0x0431
R/W
Valid between scale range maximum and minimum
Scale Point 11
1074
0x0432
R/W
>Scale point 10 to 100.0%
Display Point 11
1075
0x0433
R/W
Valid between scale range maximum and minimum
Scale Point 12
1076
0x0434
R/W
>Scale point 11 to 100.0%
Display Point 12
1077
0x0435
R/W
Valid between scale range maximum and minimum