Honeywell VCR DCP200 ユーザーズマニュアル

ページ / 184
DCP200 Profile Controller & Recorder - Product Manual
51-52-25-150, Issue 1 – April 2009
Modbus Parameters
Page 87
Parameter Name
Modbus Address
Access
Values
(Dec)
(Hex)
Master Transmit 
Format
2123
0x084B
R/W
Value
Data Format
0
Integer
1
Integer with 1 decimal place
2
Floating point number
Comms Write 
Enable/Disable
2124
0x084C
R/W
Value
Communications Status
0
Writing via serial communications disabled
1
Writing via serial communications enabled
Auxiliary Input A 
Input Signal Break
2127
0x084F
RO
Value
Auxiliary Input A Break Status
0
Inactive
1
Active
Auxiliary Input A 
Input Signal Under 
Range
2128
0x0850
RO
Value
Auxiliary Input A Under Range Status
0
Inactive
1
Active
Auxiliary Input A 
Input Signal Over 
Range
2129
0x0851
RO
Value
Auxiliary Input A Over Range Status
0
Inactive
1
Active
Option Slot B Parameters
Parameter Name
Modbus Address
Access
Values
(Dec)
(Hex)
Auxiliary Input B 
Type
2080
0x0820
R/W
Value
Auxiliary B Input Type
0
0 to 20mA DC
1
4 to 20mA DC
2
0 to 10V DC
3
2 to 10V DC
4
0 to 5V DC
5
1 to 5V DC
6
0 to 100mV DC
7
>2000 Ohm Potentiometer
Option Slot B 
Module Type
2081
0x0821
RO
Value
Module Fitted In Slot B
0
None Fitted
1
Auxiliary Input B with Digital Input B
255
Error (unrecognised module)
Auxiliary Input B 
Input Signal Break
2082
0x0822
RO
Value
Auxiliary Input B Break Status
0
Inactive
1
Active
Auxiliary Input B 
Input Signal Under 
Range
2083
0x0823
RO
Value
Auxiliary Input B Under Range Status
0
Inactive
1
Active
Auxiliary Input B 
Input Signal Over 
Range
2084
0x0824
RO
Value
Auxiliary Input B Over Range Status
0
Inactive
1
Active