          4.  Electrical Installation
  4.1  General
 
 
Danger: Turn off electrical power before servicing. Contact with live electric components can  
 
  cause shock or death.
Notice: If any of the original wire supplied with the system must be replaced, use similar wire
of the same temperature rating. Otherwise, insulation may melt or degrade, exposing bare  
wire.
 
All wiring must be in compliance with the local codes or in their absence, the National Electric Code,  
 
NFPA70. All wiring should be appropriate Class 1 wiring as follows: installed in rigid metal conduit,  
 
 
intermediate metal conduit, rigid non-metallic conduit, electrical metallic tubing, or be otherwise suitably    
 
protected from physical damage.
 
RSIB models operate at different voltages, so it’s important to pay attention to the wiring details.   
 
RSIB 300 operates at 1x120VAC while all other models can operate at 3x208-230VAC or  
 
 
 
3x440-480VAC.
  4.2 Wiring Diagram - RSIB 300
 
 
Power Venter and motor specifications can be found under “Sec. 2.1 Dimensions and Capacities”. The    
 
power venter is equipped with a variable speed motor.  The diagram below shows a typical wiring diagram  
 
for a RSIB 300 utilizing a Fan Speed Control.