TCP/IP Ethernet Communications for the Series 90™ PLC User's Manual
 
 
 May 2002 
GFK-1541B
3
 
Minor Error Codes for Major Error Code 11H (at Remote Server PLC) -
Continued
2E11H
The maximum number of transfers of this transfer type is already taking place.
2F11H
Cannot obtain a backplane transfer buffer.
3011H
Cannot obtain resources other than backplane transfer buffers.
3111H
Connection ID or block transfer ID is not valid.
3211H
Timed out waiting for PLC CPU response.
3311H
The PLC CPU aborted the request.
3411H
An invalid message type was specified.
3511H
The specified task is not registered.
3611H
The mailbox offset specified is invalid.
3711H
The backplane task could not be registered because the message response handler
was not specified.
3811H
The backplane task could not be registered because the unsolicited mailbox
message handler was not specified.
3911H
The backplane task could not be registered because a required parameter was not
specified.
3A11H
More than the allowable byte length in a single transfer.
3B11H
Bad sequence number in the request.
3C11H
Invalid command in request.
3D11H
Response length does not match length specified in the response qualifier.
3E11H
Request failed because the PLC’s Service Request Processor is not initialized.
3F11H
Request failed due to an error in the remote device, most likely running out of
Dual-Port RAM text buffers.
4011H
Unable to free dual port memory that was allocated for a connection or block
transfer area.
4111H
The backplane task could not be registered because the service request handler was
not specified.
4211H
No dual port memory was allocated for the connection or block transfer area
needed to process the request.
4311H
Failure to register with backplane driver because the requested task is already
registered.
4411H
Request failed because an invalid field was identified in the request mailbox
qualifier.
E811H
Unable to send request to the PLC because an internal message queue is full.
E911H
Unable to send request to the PLC because the text buffer type is invalid.
EA11H
Unable to send request to the PLC because the mailbox utility function is invalid.
EB11H
Unable to send request to the PLC because the mailbox message is not specified.
EC11H
Unable to send request to the PLC because the internal message queue is not
initialized.
FE11H
Request failed due to mailbox error on remote device.  The remote device log will
have more information.
Error codes specific to Series 90-30 CPU374*
2911H
The backplane driver is not initialized.
2A11H
The backplane driver could not access the PLC.
2F11H
Request failed due to an invalid parameter detected in the remote device.  The
remote device log will have more information.
3011H
The specified task is not registered.