TCP/IP Ethernet Communications for the Series 90™ PLC User's Manual
 
 
 May 2002 
GFK-1541B
2
 
LED Pattern
Where Stopped
Possible Cause
Corrective Actions
❍   OK (OFF)
❍   LAN (OFF)
❍   FDX (OFF)
❍   STAT (OFF)
A
Hardware
Failure
Fatal Hardware Error.
ƒ 
Make sure the PLC has power.
ƒ 
Examine PLC Fault Table for clues.*
ƒ 
Recheck PLC Programmer
configuration.
ƒ 
Power off baseplate, inspect the
Interface for loose components,
reseat the Interface, and Restart.
ƒ 
Try a different slot.
ƒ 
If the problem persists, replace the
Interface or PLC hardware.
✫   OK (Slowblink)
✫   LAN (Slowblink)
✫   FDX (Slowblink)
✫   STAT (Slowblink)
All LEDs blink in unison.
B
Software
Loader
ƒ 
Restart pushbutton until
bottom LED turns ON.
ƒ 
Station Manager LOAD
command issued.
ƒ 
Software corrupt.
ƒ 
Connect a PC Software Loader and
load new software. See Appendix C.
ƒ 
Cycle power  or  press Restart
pushbutton again for less than 5
seconds to restart the Interface and
clear the load request.
✫   OK (Slowblink)
❍   LAN (OFF)
❍   FDX (OFF)
❍   STAT (OFF)
C
Waiting for
Configuration
from PLC
ƒ 
Did not configure slot using
PLC Programmer.
ƒ 
New CPU with no
configuration.
ƒ 
CPU not communicating
with Ethernet Interface
ƒ 
(Condition can last a
maximum  of 2 minutes.)
ƒ 
Use PLC Programmer configuration
software to configure the Interface
then store the configuration to the
PLC CPU.
ƒ 
Make sure Interface is in the correct
slot on the baseplate.
ƒ 
Power cycle the PLC.
ƒ 
Clear faults and Restart Interface.
✫        OK (Slowblink)
/
/
 
LAN (ON/Traffic/OFF)
❍        FDX (OFF/Slowblink)
✫        STAT (Slowblink)
OK and STAT blink in unison.
D
Waiting for IP
Address
Interface’s IP address has not
been configured or has been
configured as 0.0.0.0.
ƒ 
Use PLC Programmer to configure
the Interface with a non-zero IP
address.
ƒ 
Use a BOOTP server to provide
Interface with a non-zero IP address.
✫         OK (Slowblink)
●/
/
❍  
LAN
 (ON/Traffic/OFF)
✫         FDX (Slowblink)
●/❍   STAT (ON/OFF)
OK and SER blink in unison.
E
Maintenance
ƒ 
Restart pushbutton pressed
until bottom two LEDs turn
ON.
ƒ 
Station Manager MAINT
command issued.
ƒ 
Internal System Error when
Interface was Operational
caused a restart and
entrance into Maintenance.
ƒ 
If you did not intend to enter
Maintenance press the Restart
pushbutton for less than 5 seconds.
This clears the Maintenance request.
ƒ 
Examine PLC Fault Table for clues.*
ƒ 
If you need to use the Station
Manager to troubleshoot a problem,
see GFK-1186, TCP/IP Ethernet
Communications for the Series 90
PLC Station Manager Manual.
●        OK (ON)
●/
/
❍ LAN 
(ON/Traffic/OFF)
●/❍  FDX (ON/OFF)
1
●/❍  STAT (ON/OFF)
1
 FDX should be ON if Full
Duplex mode is activated;
otherwise, it should be OFF.
F
Operational
ƒ 
If the LAN LED is OFF,
the problem may be:
ƒ 
Network cable or
transceiver not connected to
Interface or bad transceiver.
ƒ 
Network cable not
terminated properly.
ƒ 
SQE not enabled on
transceiver.
ƒ 
If the STAT LED is OFF,
an exception condition has
occurred.
ƒ 
Connect cable and transceiver
properly.  Replace transceiver.
ƒ 
Terminate  network cable properly.
ƒ 
Set SQE ON on transceiver in accord
with manufacturer’s instructions.
ƒ 
Examine PLC Fault Table to find out
why the STAT LED is OFF.  *
* Identify the PLC fault message using the PLC Programmer, then refer to Table 8-1 in Chapter 8 for corrective actions.