Precision Trading 60 R3.0 ユーザーズマニュアル

ページ / 62
Operator Manual, Supercharger 60 
R3.0 
 
Page 26 of 62 
5.4  DISCHARGE. 
NOTE: For battery voltages greater than 32V, the discharge current is automatically 
limited to 30A. A current fault condition will result if more than 30A is programmed. 
5.4.1.  ANALYSIS (AUTO CUT-OFF): 
5.4.1.1.  The battery is discharged at the selected rate for a preset time.  
5.4.1.2.  Discharge is automatically terminated (cycle end), at the end of the 
time selected or if the battery voltage reaches the equivalent of 1 
VOLT/cell (capacity failure), as determined by the number of cells 
programmed, or it is terminated as a fault, if: 
•  The actual discharge current differs from the programmed value by 
more than 1 AMP (current fault). 
•  Overheating of the transistor heat sinks is detected (overheat fault). 
•  NOTE: Discharge operation can be terminated at any time by 
depressing the (green) reset button. 
5.4.2.  DEEP CYCLE (FULL DISCHARGE): 
5.4.2.1.  The battery is discharged at the selected rate for a preset time.  
5.4.2.2.  Discharge is automatically terminated (cycle end) at the end of the time 
selected, or as a fault, if: 
•  The actual discharge current differs from the programmed value by 
more than 1 AMP (current fault). NOTE: Undercurrent fault 
monitoring is disabled at battery voltages below 2V.
 
•  Overheating of the transistor heat sinks is detected (overheat fault).