3. Installation
RuggedCom® RuggedBackbone™
26
RX1510 Installation Guide Rev 104
Cabling Category
1000Base-
TX Compliant
Required Action
< 5
No
New wiring infrastructure required.
5
Yes
Verify TIA/EIA-568-A compliance.
5e
Yes
No action required. New installations should be designed with Category 5e or higher.
6
Yes
No action required.
> 6
Yes
Connector and wiring standards to be determined.
Table 3.4. Cabling Categories and 1000Base-TX Compliance
Follow these recommendations for copper data cabling in high electrical noise environments:
• Data cable lengths should be as short as possible, ideally limited to 10' (3m) in length. Copper
data cables should not be used for inter-building communications.
• Power and data cables should not be run in parallel for long distances, and should be installed
in separate conduits. Power and data cables should intersect at 90° angles when necessary
to reduce inductive coupling.
• Optionally, shielded/screened cabling can be used. The cable shield should be grounded at one
single point to avoid the generation of ground loops.
3.7.3. Transient Suppression
All  copper  Ethernet  ports  on  RuggedCom  products  include  transient  suppression  circuitry  to
protect  against  damage  from  electrical  transients  and  to  ensure  conformance  to  IEC  61850-3
and  IEEE  1613  Class  1.  This  means  that  during  a  transient  electrical  event,  it  is  possible  for
communications errors or interruptions to occur, but recovery is automatic.
RuggedCom does not recommend the use of copper cabling of any length for critical,
real-time, substation automation applications.
RuggedCom  also  recommends  against  the  use  of  copper  Ethernet  connections  to  interface  to
devices in the field across distances which could produce high levels of ground potential rise (that
is, greater than 2500V), during line-to-ground fault conditions.