FieldServer FS-8700-72 ユーザーズマニュアル
FS-8700-72 Secutron Manual
Page 10 of 15
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web: www.fieldserver.com
Tel: (408) 262-2299 Fax: (408) 262-2269 Toll Free: 888-509-1970 email: support@fieldserver.com
5.2.
Server Side Connection Descriptors
Section Title
Connections
Column Title
Function
Legal Values
Port
Specify which port the device is connected
to the FieldServer
to the FieldServer
P1-P8
2
Baud*
Specify baud rate
150, 300, 1200, 2400, 4800, 9600
(Vendor limitation)
(Vendor limitation)
Parity*
Specify parity
None (Vendor limitation)
Data_Bits*
Specify data bits
8 (Vendor limitation)
Stop_Bits*
Specify stop bits
1 (Vendor limitation)
Protocol
Specify protocol used
Secutron
Handshaking* Specify hardware handshaking
None
Example
//
Server Side Connections
Connections
Port,
Protocol,
Baud,
Parity,
Handshaking
P1,
Secutron,
9600,
None,
None
5.3.
Server Side Node Descriptors
Section Title
Nodes
Nodes
Column
Title
Function
Legal Values
Node_Name
Provide name for Node
Up
to
32
alphanumeric
characters
Node_ID
Generic Node ID unique to port. Also used as panel
number.
number.
0-9
Protocol
Specify protocol used
Secutron
Port
Port to which node belongs
P1-P8
Example
// Server Side Nodes
Nodes
Node_Name,
Node_ID,
Protocol,
Connection
Node_1,
1,
Secutron,
P1
2
Not all ports shown are necessarily supported by the hardware. Consult the appropriate Instruction
manual for details of the ports available on specific hardware.