All installations and services must be performed by qualified service personnel.
 
 14
?
?
?
?CAUTION:  A permanent opening with a minimum of 50 square inches of 
unobstructed infiltration (free area) for ventilation and combustion air must be 
provided to the interior of the structure.  Additional make-up air may need to be 
supplied to the interior of the structure to compensate for exhaust fans, 
appliances, or vents, which consume air from the interior of the structure. 
 
Refer to the assembly installation instructions included with OM1COT-BASE cottage 
base for additional information. 
 
3.  Coil Cabinet: CE111S 
 
The CE111S coil cabinet (figure 1C) is for applications requiring air conditioning.  
The coil cabinet is designed to have the combustion air brought in from the bottom 
thru a duct, supplied with the cabinet.  Refer to section G Combustion air of this 
manual for further instructions on the combustion air termination and connections.  
For additional information refer instructions provided with the CE111S coil cabinet. 
 
 
 
 
 
 
E.  ALCOVE INSTALLATION 
 
In this application, a minimum of 18 
inches of clearance must be provided 
to the front of the unit.  Refer to Figure 
4. 
 
Alcove installations must use the No. 
70 mobile home base.  
 
Refer to section  
G. COMBUSTION AIR 
for additional 
combustion air requirements. 
 
 
 
 
 
 
                                                                              
Figure 4